AAAC, Stranded All Alloy Aluminum Conductor, overhead line bared alloy aluminum

Applications

AAAC conductor is also known as aluminium stranded conductor. All aluminium conductors are made up of one or more strands of aluminium wire depending on the end usage.It is manufactured from electronically refined aluminium. Specially suitable for application in:

  power transmission and primary &secondary distribution lines

●  laying across basins, rivers and valleys

 For any more information or advice please contact the office on 0086-18832134509(WhatsApp/WeChat)


Share:

Details

Overview

Stranded All Alloy Aluminum Conductor

The stranded All Alloy Aluminium Conductor (AAAC) are made up of concentric-lay-stranded alloy aluminium wires only.
The conductor may be made up of 7, 19, 37, 61 or more wires in 1, 2, 3, 4 or more layers around a central wire. Each successive layer shall have six more wires than the layer immediately beneath. For a given cross sectional area, the conductor becomes more flexible as the number of wires is increased(with a corresponding decrease in size of each wire). Being lighter, alloy conductors can sometimes be used to advantage in place of the more conventional ACSR; Having lower breaking loads than the later, their use becomes particularly favourable when ice and wind loadings are low

Construction

AAAC, Stranded All Alloy Aluminum Conductor, overhead line bared alloy aluminum

Conductor Sections

 AAAC, Stranded All Alloy Aluminum Conductor, overhead line bared alloy aluminum

Description:  AAAC, Stranded All Alloy Aluminum Conductor  

Conductor:  Alloy Aluminum Conductor

Standards

GB/T1179/IEC61089/BS EN50182/DIN48201-6/ASTM B 399/BS 3242

Technical Data 

                             IEC 60189(*if other standards are required,please contact us)
CODENOMINAL     AREASTRANDINGOVERALL      DIAMETERWEIGHTRATED      STRENGTHELECTRICAL RE515TANCECURRENT      RATING

mm²No.xmmmmkg/kmKNΩ/KMA
1618.47/1.835.4950.45.431.789686
2528.87/2.296.8778.78491.1453113
40467/2.898.67125.913.580.7158151
6372.57/3.6310.89198.321.390.4545200
10011519/2.7813.9316.333.950.2877266
12514419/3.115.5395.442.440.2302305
16018419/3.5117.55506.154.320.1798355
20023019/3.9319.65632.767.910.1439407
25028819/4.3921.95790.884.880.1151466
31536337/3.5324.71998.9106.950.0916535
40046037/3.9827.861268.4135.810.0721618
45051837/4.2229.541426.9152.790.0641663
50057537/4.4531.151585.5169.760.0577706
56064561/3.6733.031778.4190.140.0516755
63072561/3.8935.012000.7213.90.0458809
71081761/4.1337.172254.8241.070.0407866
80092161/4.3839.422540.6271.620.0361928
900*103691/3.8141.912861.1305.580.0321992
1000*115191/4.0144.113179339.530.02891051
1120*128991/4.2546.753560.5380.270.02581118
1250*143991/4.4949.393973.7424.410.02311185
BS EN50182(*if other standards are required, please contact us)
CODESTRANDINGNOMINAL AREAOVERALL DIAMETERWEIGHTRATED STRENGTHELECTRICAL RESISTANCECURRENT RATING

No.xmmmm²mmKg/kmKNΩ/KMA
Box7/1.8518.85.5551.45.551,74887
Acecia7/2.0823.86.2464.97.021.3828101
Almond7/2.3430.17.0282.28.881.0926116
Cedar7/2.5435.57.6296.810.460,9273129
Deodar7/2.7742.28.31115.212.440,7797143
Pr7/2.9547.88.85130.614.110,6875155
Hamel7/3.3059.99.9163.417.660.5494178
Pine7/3.6171.610.83195.621.140,4591199
Holy7/3.9184.111.73229.524.790.3913219
Wlow7/4.0489.712.1224526.470,3665228
OK7/4.65118.913.95324.535.070,2767272
Muberry19/3.18150.915.9414.344.520.2192314
Ash19/3.48180.717.4496.153.310,183351
Bm19/3.7621118.8579.262.240,1568386
Popler37/2.87239.420.09659.470.610,1387416
Sycamore37/3.23303.222.61835.289.40.1095480
Uses37/3.53362.124.71998106.820.0917535
YeW37/4.0647928.421319.6141.310,0693633
Totara37/4.14498.128.981372.1146.930,0666648
Rubus61/3.50586.931.51622173.130,0567714
Sorbus61/3.71659.433.391822.5194.530,0505764
Areucaria61/4.14821.137.262269.4242.240.0406868
Redaced61/4.56996.241.042753.2293.880.0334970



Contact Us Now