The cables are mainly used for:
· Indoors and in cable ducts
· Outdoors,underground and in water
· in power supply stations
· Transformer stations
· Industrial Plants
Due to the good laying characteristic, this cable can also be installed in difficult line guideways.
The inner conducting layer between the conductor and the XLPE insulation and the firmly bonded outer conducting layer on the XLPE insulation assures a construction free of partial discharges with high operational reliabilities.
For any more information or advice please contact the office on 0086-13229065196(WhatsApp/WeChat)
Details
CU/XLPE/STA/PVC Cable
Medium voltage three core cable is suitable for use in power networks, in fixed installation outdoors in cable ducts or directly in the ground. Cable operational stability is enhanced because of very low dielectric loss factor, excellent insulation property of XLPE and firm bonding with conductor screen and insulation screen of semi-conductive material (extruded in one process), which makes it widely used in transformer stations, electric power plants and industrial plants.
Descriptions:N2XSEBY Three Core MV Power Cable
Conductor:Copper, Class2,Circular compacted conductors
Conductor Screen: Non-metallic,semi-conducting compound
Insulation: Cross-linked polyethylene XLPE
Insulation Screen: Non-metallic,semi-conducting compound
Metallic Screen: Copper Tape
Filler: Non-hygroscopic Material
Binder Tape: Non-hygroscopic Material
Armouring: Steel Tape Armour
Outer Sheath: Polyvinyl Chloride PVC&Polyethylene PE&LSZH
Physical Properties
Operating Temperature: up to 70℃(PVC insulation); up to 90℃(XLPE insulation)
Temperature Range: -5℃(PVC or LSZH sheath); -20℃(PE sheath)
Short Circuit Temperature(5 seconds maximum duration): 140℃-160℃(PVC insulation);250℃(XLPE insulation)
Nominal Voltages:U0/U 1.8/3kV , 6/10 kV, 12/20 kV, 18/30 kV
Three Core Cable(N2XSEBY)-6/10KV | |||||||
No. of cores and nominal cross section | Thickness of Insulation | Thickness of sheath | Approx. Overall Diameter | Approx. Weight | Max. DC Resistance of conductor(20℃) | Current Carrying Capacity | |
mm2 | mm | mm | mm | kg/km | Ω/km | in air(A) | in ground(A) |
3Cx35 | 3.4 | 2.4 | 50 | 3500 | 0.5240 | 154 | 151 |
3Cx50 | 3.4 | 2.5 | 53 | 4000 | 0.3870 | 183 | 178 |
3Cx70 | 3.4 | 2.6 | 57 | 5000 | 0.2680 | 225 | 215 |
3Cx95 | 3.4 | 2.7 | 60 | 5850 | 0.1930 | 272 | 257 |
3Cx120 | 3.4 | 2.9 | 64 | 7150 | 0.1530 | 310 | 290 |
3Cx150 | 3.4 | 3.0 | 68 | 8200 | 0.1240 | 348 | 323 |
3Cx185 | 3.4 | 3.1 | 71 | 9300 | 0.0991 | 396 | 363 |
3Cx240 | 3.4 | 3.3 | 78 | 11500 | 0.0754 | 462 | 418 |
3Cx300 | 3.4 | 3.4 | 83 | 13550 | 0.0601 | 523 | 467 |
3Cx400 | 3.4 | 3.6 | 86 | 17400 | 0.0470 | 582 | 515 |
Three Core Cable(N2XSEBY)-8.7/15KV | |||||||
No. of cores and nominal cross section | Thickness of Insulation | Thickness of sheath | Approx. Overall Diameter | Approx. Weight | Max. DC Resistance of conductor(20℃) | Current Carrying Capacity | |
mm2 | mm | mm | mm | kg/km | Ω/km | in air(A) | in ground(A) |
3Cx35 | 4.5 | 2.6 | 55 | 4100 | 0.5240 | 154 | 151 |
3Cx50 | 4.5 | 2.7 | 57 | 4500 | 0.3870 | 183 | 178 |
3Cx70 | 4.5 | 2.8 | 61 | 5500 | 0.2680 | 225 | 215 |
3Cx95 | 4.5 | 2.9 | 66 | 6500 | 0.1930 | 272 | 257 |
3Cx120 | 4.5 | 3.0 | 69 | 7600 | 0.1530 | 310 | 290 |
3Cx150 | 4.5 | 3.1 | 73 | 8700 | 0.1240 | 348 | 323 |
3Cx185 | 4.5 | 3.3 | 77 | 9950 | 0.0991 | 396 | 363 |
3Cx240 | 4.5 | 3.4 | 81 | 12200 | 0.0754 | 462 | 418 |
3Cx300 | 4.5 | 3.6 | 88 | 15000 | 0.0601 | 523 | 467 |
3Cx400 | 4.5 | 3.8 | 92 | 18500 | 0.0470 | 582 | 515 |
Three Core Cable(N2XSEBY)-12/20KV | |||||||
No. of cores and nominal cross section | Thickness of Insulation | Thickness of sheath | Approx. Overall Diameter | Approx. Weight | Max. DC Resistance of conductor(20℃) | Current Carrying Capacity | |
mm2 | mm | mm | mm | kg/km | Ω/km | in air(A) | in ground(A) |
3Cx35 | 5.5 | 2.8 | 59 | 4300 | 0.5240 | 154 | 151 |
3Cx50 | 5.5 | 2.9 | 62 | 5000 | 0.3870 | 183 | 178 |
3Cx70 | 5.5 | 3.0 | 66 | 5800 | 0.2680 | 225 | 215 |
3Cx95 | 5.5 | 3.2 | 68 | 7000 | 0.1930 | 272 | 257 |
3Cx120 | 5.5 | 3.3 | 70 | 7850 | 0.1530 | 310 | 290 |
3Cx150 | 5.5 | 3.4 | 74 | 9150 | 0.1240 | 348 | 323 |
3Cx185 | 5.5 | 3.5 | 80 | 10500 | 0.0991 | 396 | 363 |
3Cx240 | 5.5 | 3.7 | 88 | 13550 | 0.0754 | 462 | 418 |
3Cx300 | 5.5 | 3.9 | 92 | 15850 | 0.0601 | 523 | 467 |
3Cx400 | 5.5 | 4.0 | 96 | 18300 | 0.0470 | 582 | 515 |
Three Core Cable(N2XSEBY)-18/30KV,19/33KV | |||||||
No. of cores and nominal cross section | Thickness of Insulation | Thickness of sheath | Approx. Overall Diameter | Approx. Weight | Max. DC Resistance of conductor(20℃) | Current Carrying Capacity | |
mm2 | mm | mm | mm | kg/km | Ω/km | in air(A) | in ground(A) |
3Cx50 | 8.0 | 3.2 | 75 | 6650 | 0.3870 | 183 | 178 |
3Cx70 | 8.0 | 3.3 | 78 | 7650 | 0.2680 | 225 | 215 |
3Cx95 | 8.0 | 3.5 | 83 | 8700 | 0.1930 | 272 | 257 |
3Cx120 | 8.0 | 3.6 | 87 | 10700 | 0.1530 | 310 | 290 |
3Cx150 | 8.0 | 3.7 | 90 | 11750 | 0.1240 | 348 | 323 |
3Cx185 | 8.0 | 3.9 | 94 | 13500 | 0.0991 | 396 | 363 |
3Cx240 | 8.0 | 4.0 | 100 | 15500 | 0.0754 | 462 | 418 |
3Cx300 | 8.0 | 4.2 | 106 | 17800 | 0.0601 | 523 | 467 |