Contact
Applications
Aerial Bundle Cables, often referred to as Aerial Bundled Conductors or simply ABC Cable, are cables for overhead line power, so called for combining multiple single core cables together. Its mainly applications are:
● For distribution low power overhead networks in metropolitan,urban and rural areas;
● For supply of remote facilities and villages of temporary and permanent character;
● For above-ground house connections.
● In temporary power installations such as on construction sites
For any more information or advice, please contact the office on 0086-18832134509 (WhatsApp/WeChat)
Details
Copper Overhead Service Drop Cable Wires
overhead cable is a special cable manufactured using a process similar to that of cross-linked cables. it is a new way of transmitting electricity between overhead conductors and underground cables. overhead cables are widely used in power transmission at home and abroad. Primarily used for 120 volt overhead service applications such as street lighting, outdoor lighting, and temporary service for construction. To be used at voltages of 600 volts phase-to-phase or less and at conductor temperatures of 75 ºC for polyethylene insulated conductors,90°C for crosslinked polyethylene (XLP) insulated conductors. It is ideal for use in urban areas with congested power distribution and narrow lanes and by-lanes . The flexible system is much easier than conventional overhead power lines to re-route when demanded by changes in urban development plans. And generally overhead insulated cables are high-voltage lines , so if they are very close to buildings, they must choose overhead insulated cables.Aerial Bundled Conductor cables can be used to replace bare conductor cables in overhead distribution systems.
Construction
Description: Overhead Service Drop Cable Wires
Conductor: Class 2 Stranded Copper Conductor
+N-: With “Messenger” Core
Insulation: HDPE or XLPE Insulation
Insulation Color: Black
Rated Voltage (Uo/U): 0.6/1KV
Physical Properties
Maximal operating conductor Temperature: up to 75℃(HDPE insulation) 90℃(XLPE insulation)
Minimum Temperature for cable laying: -5℃(XLPE insulation)
Short Circuit Temperature(5 seconds maximum duration): 250℃(XLPE insulation)
Technical Data
PHYSICAL PROPERTIES | ELECTRICAL PROPERTIES | ||||||
Cable Size | Insulation Thickness | Approx Twisted Diameter | Approx. Net.Weight | Max.Conductor Resistance at 20℃ | Current Carrying Capacity at 35℃ | Calculated Breaking Force | Standard Length |
mm² | mm | mm | Kg/km | Ω/km | A | kg | m |
2x6rm | 1.2 | 13.0 | 136 | 3.080 | 54 | 394 | 2000 |
2x10rm | 1.2 | 14.0 | 211 | 1.830 | 73 | 656 | 2000 |
2x16rm | 1.2 | 16.0 | 334 | 1.150 | 97 | 1,051 | 1000 |
4x6rm | 1.2 | 15.7 | 258 | 3.080 | 54 | 788 | 1000 |
4x10rm | 1.2 | 170 | 422 | 1.830 | 73 | 1,312 | 1000 |
4x16rm | 1.2 | 190 | 640 | 1.150 | 97 | 2,102 | 1000 |
4x25rm | 1.4 | 240 | 1,008 | 0.727 | 133 | 3,284 | 1000 |