AL/XLPE/PVC cables are used for electricity supply in low voltage installation system, they are suitable for:
● installation in indoors and outdoors
● in cable ducts
● underground
● in power and switching stations
● local energy distributions
● industrial plants
where there is no risk of mechanical damage.
For any more information or advice please contact the office on 0086-18832134509(WhatsApp/WeChat)
Details
The 0.6/1 KV AL/XPLE/PVC cable plays a vital role in low-voltage power transmission and distribution, widely applied in building,industrial, and infrastructure settings to ensure the reliability and safety of power systems. This Power Cable with stranded compacted aluminum conductor(CU), cross-linked polyethylene insulation (XPLE), and a polyvinyl chloride sheath (PVC). For fixed installation in interiors,outdoor installation,in soil,in water and concrete,if no posterior mechanical damage is to be expected.
Construction
Description: NA2XY, XLPE Insulated Aluminum Power Cable
Conductors: Class 1 or Class 2 of plain aluminum, in accordance with IEC 60228.
Insulation: Cross-linked polyethylene XLPE
Insulation Colour: Natural or as required
Filler: Non-hygroscopic Material
Outer Sheath: Extruded Polyvinyl Chloride PVC&Polyethylene PE&LSZH
Colour of Sheath: Black
Voltage Rating (Uo/U): 600/1000V Test Voltage: 3.5kV for 5 minutes
Physical Properties
Maximal operating conductor Temperature: up to 70℃(PVC insulation); up to 90℃(XLPE insulation)
Operating Temperature Range: -5℃(PVC or LSZH sheath); -20℃(PE sheath)
Short Circuit Temperature(5 seconds maximum duration): 140℃-160℃(PVC insulation);250℃(XLPE insulation)
Technical Data
0.6/1kV-3+1 core aluminum conductor XLPE insulated PVC sheathed power cable | |||||||
No. of cores and nominal cross section | Thickness of Insulation | Thickness of Sheath | Approx. overall Diameter | Approx. weight | Max. DC resistance of conductor(20℃) | Current carrying capacity | |
(mm2) | (mm) | (mm) | (mm) | (kg/km) | (Ω/km) | In Air(A) | In Ground(A) |
3X16+1X10 | 0.7/0.7 | 1.8 | 19.4 | 370 | 1.91/3.08 | 65 | 85 |
3X25+1X16 | 0.9/0.7 | 1.8 | 22.8 | 520 | 1.20/1.91 | 87 | 110 |
3X35+1X16 | 0.9/0.7 | 1.8 | 25.1 | 650 | 0.868/1.91 | 105 | 130 |
3X50+1X25 | 1.0/0.9 | 1.8 | 28.2 | 780 | 0.641/1.20 | 130 | 160 |
3X70+1X35 | 1.1/0.9 | 1.9 | 31.9 | 1050 | 0.443/0.868 | 165 | 195 |
3X95+1X50 | 1.1/1.0 | 2.1 | 35.7 | 1460 | 0.320/0.641 | 205 | 235 |
3X120+1X70 | 1.2/1.1 | 2.2 | 39.6 | 1820 | 0.253/0.443 | 240 | 265 |
3X150+1X70 | 1.4/1.1 | 2.3 | 43.6 | 2150 | 0.206/0.443 | 270 | 300 |
3X185+1X95 | 1.6/1.1 | 2.5 | 49.8 | 2725 | 0.164/0.320 | 315 | 340 |
3X240+1X120 | 1.7/1.2 | 2.7 | 55.3 | 3480 | 0.125/0.253 | 375 | 395 |
3X300+1X150 | 1.8/1.4 | 2.9 | 57.0 | 4230 | 0.100/0.206 | 435 | 445 |
3X400+1X185 | 2.0/1.7 | 3.1 | 70.0 | 5520 | 0.0778/0.164 | 510 | 510 |
0.6/1kV-4+1 core aluminum conductor XLPE insulated PVC sheathed power cable | |||||||
No. of cores and nominal cross section | Thickness of Insulation | Thickness of Sheath | Approx. overall Diameter | Approx. weight | Max. DC resistance of conductor(20℃) | Current carrying capacity | |
(mm2) | (mm) | (mm) | (mm) | (kg/km) | (Ω/km) | In Air(A) | In Ground(A) |
4X16+1X10 | 0.7/0.7 | 1.8 | 21.3 | 450 | 1.91/3.08 | 65 | 85 |
4X25+1X16 | 0.9/0.7 | 1.8 | 25.7 | 650 | 1.20/1.91 | 87 | 110 |
4X35+1X16 | 0.9/0.7 | 1.8 | 28.2 | 795 | 0.868/1.91 | 105 | 130 |
4X50+1X25 | 1.0/0.9 | 1.9 | 28.9 | 1020 | 0.641/1.20 | 130 | 160 |
4X70+1X35 | 1.1/0.9 | 2.0 | 32.2 | 1360 | 0.443/0.868 | 165 | 195 |
4X95+1X50 | 1.1/1.0 | 2.2 | 36.9 | 1870 | 0.320/0.641 | 205 | 235 |
4X120+1X70 | 1.2/1.1 | 2.3 | 40.8 | 2342 | 0.253/0.443 | 240 | 265 |
4X150+1X70 | 1.4/1.1 | 2.5 | 44.7 | 2778 | 0.206/0.443 | 270 | 300 |
4X185+1X95 | 1.6/1.1 | 2.7 | 50.7 | 3495 | 0.164/0.320 | 315 | 340 |
4X240+1X120 | 1.7/1.2 | 2.9 | 56.4 | 4416 | 0.125/0.253 | 375 | 395 |
4X300+1X150 | 1.8/1.4 | 3.1 | 64.0 | 5422 | 0.100/0.206 | 435 | 445 |
0.6/1kV-3+2 core aluminum conductor XLPE insulated PVC sheathed power cable | |||||||
No. of cores and nominal cross section | Thickness of Insulation | Thickness of Sheath | Approx. overall Diameter | Approx. weight | Max. DC resistance of conductor(20℃) | Current carrying capacity | |
(mm2) | (mm) | (mm) | (mm) | (kg/km) | (Ω/km) | In Air(A) | In Ground(A) |
3X16+2X10 | 0.7/0.7 | 1.8 | 20.8 | 425 | 1.91/3.08 | 65 | 85 |
3X25+2X16 | 0.9/0.7 | 1.8 | 25.2 | 600 | 1.20/1.91 | 87 | 110 |
3X35+2X16 | 0.9/0.7 | 1.8 | 26.8 | 720 | 0.868/1.91 | 105 | 130 |
3X50+2X25 | 1.0/0.9 | 1.9 | 28.7 | 955 | 0.641/1.20 | 130 | 160 |
3X70+2X35 | 1.1/0.9 | 2.0 | 33.7 | 1230 | 0.443/0.868 | 165 | 195 |
3X95+2X50 | 1.1/1.0 | 2.2 | 38.3 | 1706 | 0.320/0.641 | 205 | 235 |
3X120+2X70 | 1.2/1.1 | 2.3 | 43.2 | 2180 | 0.253/0.443 | 240 | 265 |
3X150+2X70 | 1.4/1.1 | 2.4 | 46.5 | 2525 | 0.206/0.443 | 270 | 300 |
3X185+2X95 | 1.6/1.1 | 2.6 | 51.9 | 3195 | 0.164/0.320 | 315 | 340 |
3X240+2X120 | 1.7/1.2 | 2.8 | 58.0 | 4050 | 0.125/0.253 | 375 | 395 |
3X300+2X150 | 1.8/1.4 | 3.0 | 64.2 | 4983 | 0.100/0.206 | 435 | 445 |