AL/XLPE/STA/PVC 600/1000V NA2XBY Cable

Applications

NA2XBY cables are designed for local distribution systems and for delivering power and auxiliary control in the Building and Construction industry with a voltage rating of 0.6/1kV, which can be used   

 in fixed industrial power applications

 underground tunnels

 in power and switching stations

 local energy distributions

 industrial plants

Using steel tape armouring offers great mechanical protection, making it rigid with a large radius in installation indoors and outdoors.

For any more information or advice please contact the office on 0086-18832134509(WhatsApp/WeChat)

Share:

Details

600/1000V,XLPE Insulated Cables, With steel armoured,PVC Sheath

NA2XBY cables are designed for local distribution systems and for delivering power and auxiliary control in the building and construction industry with a voltage rating of 0.6/1kV.The NA2XBY is resistant to mechanical stresses as a result of the double layer of galvanized steel tape armour applied to the cable. The STA provides improved flexibility compared to round steel wires or other more rigid armouring.

With a flame retardant PVC outer sheath, the NA2XBY cable is suitable for fixed installations internally. The UV resistance makes external applications also permissible.  0.6/1 KV AL/XPLE/STA/PVC cable plays a vital role in low-voltage power transmission and distribution, widely applied in building,industrial, and infrastructure settings to ensure the reliability and safety of power systems. This Power Cable with stranded compacted copper conductor is composed of aluminum conductor (AL), cross-linked polyethylene insulation (XPLE), steel tape armoring for mechanical protection and a polyvinyl chloride sheath (PVC). For fixed installation in interiors,outdoor installation,in soil and concrete,if no posterior mechanical damage is to be expected.

Construction

AL/XLPE/STA/PVC 600/1000V NA2XBY Cable

Description: NA2XBY, XLPE Insulated Aluminum Power Cable   

Conductors: Class 1 or Class 2 of plain aluminum,or of Class 5 of plain aluminum in accordance with IEC 60228.

Insulation: Cross-linked polyethylene XLPE

Insulation Colour: Natural or as required

Filler:  Non-hygroscopic Material

Inner Sheath: Polyvinyl Chloride PVC

Outer Sheath: Extruded Polyvinyl Chloride PVC&Polyethylene PE&LSZH

Colour of Sheath:  Black

Voltage Rating (Uo/U): 600/1000V       Test Voltage: 3.5kV for 5 minutes

Physical Properties

Maximal operating conductor Temperature: up to 70℃(PVC insulation); up to 90℃(XLPE insulation)

Operating Temperature Range: -5℃(PVC or LSZH sheath); -20℃(PE sheath)

Short Circuit Temperature(5 seconds maximum duration): 140℃-160℃(PVC insulation);250℃(XLPE insulation)

Technical Data

                          0.6/1kV-3+1core aluminum conductor XLPE insulated steel tape armored PVC sheathed power cable
Nominal cross sectional areaInsulation thicknessNon-magnetic steel tape thickness Sheath thicknessApproximate outer diameterApprox.
weight
Max.D.C resistance of conductor(20℃)Current carrying capacity 
mm2mmmmmmmmkg/kmΩ/kmIn Air(A)In Ground(A)
3X4+1X2.50.7/0.70.21.815.5318 7.41/12.1-30 
3X6+1X40.7/0.70.21.816.8371 4.61/7.41-38 
3X10+1X60.7/0.70.21.819.3478 3.08/4.6150 47 
3X16+1X100.7/0.70.21.822.1615 1.91/3.0864 62 
3X25+1X160.9/0.70.21.825.1794 1.2/1.9186 78 
3X35+1X160.9/0.70.21.8 26.8926 0.868/1.91105 94 
3X50+1X251/0.90.21.9 30.21175 0.641/1.2125 110 
3X70+1X351.1/0.90.22.0 35.11570 0.443/0.868165 135 
3X95+1X501.1/1.00.52.2 40.42359 0.32/0.641200 160 
3X120+1X701.2/1.10.52.3 452886 0.253/0.443235 185 
3X150+1X701.4/1.10.52.5 49.13396 0.206/0.443270 205 
3X185+1X951.6/1.10.52.8 54.34070 0.164/0.32310 235 
3X240+1X1201.7/1.20.52.8 59.14855 0.125/0.253365 260 
3X300+1X1501.8/1.40.53.0 666028 0.1/0.206420 290 









0.6/1kV-4+1core aluminum conductor XLPE insulated steel tape armored PVC sheathed power cable
Nominal cross sectional areaInsulation thicknessNon-magnetic steel tape thickness Sheath thicknessApproximate outer diameterApprox.
weight
Max.D.C resistance of conductor(20℃)Current carrying capacity 
mm2mmmmmmmmkg/kmΩ/kmIn Air(A)In Ground(A)
4X4+1X2.50.7/0.70.21.816.3365 7.41/12.1-30 
4X6+1X40.7/0.70.21.817.7429 4.61/7.41-38 
4X10+1X60.7/0.70.21.820.3561 3.08/4.6150 47 
4X16+1X100.7/0.70.21.824728 1.91/3.0864 62 
4X25+1X160.9/0.70.21.828.1974 1.2/1.9186 78 
4X35+1X160.9/0.70.21.9 29.61134 0.868/1.91105 94 
4X50+1X251/0.90.22.0 341505 0.641/1.2125 110 
4X70+1X351.1/0.90.52.2 40.32351 0.443/0.868165 135 
4X95+1X501.1/1.00.52.3 44.82907 0.32/0.641200 160 
4X120+1X701.2/1.10.52.6 50.23588 0.253/0.443235 185 
4X150+1X701.4/1.10.52.8 54.64215 0.206/0.443270 205 
4X185+1X951.6/1.10.52.9 60.55133 0.164/0.32310 235 
4X240+1X1201.7/1.20.53.0 67.16289 0.125/0.253365 260 
4X300+1X1501.8/1.40.53.2 73.77544 0.1/0.206420 290 









0.6/1kV-3+2 core aluminum conductor XLPE insulated steel tape armored PVC sheathed power cable
Nominal cross sectional areaInsulation thicknessNon-magnetic steel tape thickness Sheath thicknessApproximate outer diameterApprox.
weight
Max.D.C resistance of conductor(20℃)Current carrying capacity 
mm2mmmmmmmmkg/kmΩ/kmIn Air(A)In Ground(A)
3X4+2X2.50.7/0.70.21.816.6354 7.41/12.1-30 
3X6+2X40.7/0.70.21.818416 4.61/7.41-38 
3X10+2X60.7/0.70.21.820.9531 3.08/4.6150 47 
3X16+2X100.7/0.70.21.824694 1.91/3.0864 62 
3X25+2X160.9/0.70.21.828.1920 1.2/1.9186 78 
3X35+2X160.9/0.70.21.9 29.61034 0.868/1.91105 94 
3X50+2X251/0.90.22.0 341400 0.641/1.2125 110 
3X70+2X351.1/0.90.52.2 40.32153 0.443/0.868165 135 
3X95+2X501.1/1.00.52.3 44.82658 0.32/0.641200 160 
3X120+2X701.2/1.10.52.5 50.23329 0.253/0.443235 185 
3X150+2X701.4/1.10.52.6 54.63790 0.206/0.443270 205 
3X185+2X951.6/1.10.52.8 60.54575 0.164/0.32310 235 
3X240+2X1201.7/1.20.53.0 67.15564 0.125/0.253365 260 
3X300+2X1501.8/1.40.53.2 73.76801 0.1/0.206420 290 