Contact
Applications
AL/XLPE/PVC cables are used for electricity supply in low voltage installation system, they are suitable for:
● installation in indoors and outdoors
● in cable ducts
● underground
● in power and switching stations
● local energy distributions
● industrial plants
where there is no risk of mechanical damage.
For any more information or advice, please contact the office on 0086-18832134509(WhatsApp/WeChat)
Details
XLPE Insulated,PVC Sheathed Cable,0.6/1kV
The 0.6/1 KV AL/XPLE/PVC cable plays a vital role in low-voltage power transmission and distribution, widely applied in building,industrial, and infrastructure settings to ensure the reliability and safety of power systems. This Power Cable with stranded compacted aluminum conductor(AL), cross-linked polyethylene insulation (XPLE), and a polyvinyl chloride sheath (PVC). For fixed installation in interiors,outdoor installation,in soil,in water and concrete,if no posterior mechanical damage is to be expected.
Construction
Description: NA2XY, XLPE Insulated Aluminum Power Cable
Conductors: Class 1 or Class 2 of plain aluminum, in accordance with IEC 60228.
Insulation: Cross-linked polyethylene XLPE
Insulation Colour: Natural or as required
Filler: Non-hygroscopic Material
Outer Sheath: Extruded Polyvinyl Chloride PVC&Polyethylene PE&LSZH
Colour of Sheath: Black
Voltage Rating (Uo/U):600/1000V Test Voltage: 3.5kV for 5 minutes
Physical Properties
Maximal operating conductor Temperature: up to 70℃(PVC insulation); up to 90℃(XLPE insulation)
Operating Temperature Range: -5℃(PVC or LSZH sheath); -20℃(PE sheath)
Short Circuit Temperature(5 seconds maximum duration): 140℃-160℃(PVC insulation);250℃(XLPE insulation)
Technical Data
0.6/1kV-2 core aluminum conductor XLPE insulated PVC sheathed power cable | |||||||
No. of cores and nominal cross section | Thickness of Insulation | Thickness of Sheath | Approx. overall Diameter | Approx. weight | Max. DC resistance of conductor(20℃) | Current carrying capacity | |
(mm2) | (mm) | (mm) | (mm) | (kg/km) | (Ω/km) | In Air(A) | In Ground(A) |
2X10 | 0.7 | 1.8 | 15.4 | 200 | 3.08 | 58 | 78 |
2X16 | 0.7 | 1.8 | 17.4 | 270 | 1.91 | 75 | 100 |
2X25 | 0.9 | 1.8 | 20.5 | 380 | 1.20 | 100 | 130 |
2X35 | 0.9 | 1.8 | 22.5 | 480 | 0.868 | 120 | 155 |
2X50 | 1.0 | 1.8 | 20.3 | 490 | 0.641 | 150 | 185 |
2X70 | 1.1 | 1.8 | 23.3 | 630 | 0.443 | 190 | 225 |
2X95 | 1.1 | 1.9 | 26.2 | 820 | 0.320 | 235 | 275 |
2X120 | 1.2 | 2.0 | 29.4 | 1000 | 0.253 | 275 | 315 |
2X150 | 1.4 | 2.2 | 32.6 | 1250 | 0.206 | 315 | 350 |
2X185 | 1.6 | 2.3 | 36.0 | 1540 | 0.164 | 365 | 395 |
0.6/1kV-3 core aluminum conductor XLPE insulated PVC sheathed power cable | |||||||
No. of cores and nominal cross section | Thickness of Insulation | Thickness of Sheath | Approx. overall Diameter | Approx. weight | Max. DC resistance of conductor(20℃) | Current carrying capacity | |
(mm2) | (mm) | (mm) | (mm) | (kg/km) | (Ω/km) | In Air(A) | In Ground(A) |
3X10 | 0.7 | 1.8 | 17.2 | 250 | 3.08 | 50 | 66 |
3X16 | 0.7 | 1.8 | 19.4 | 330 | 1.91 | 65 | 85 |
3X25 | 0.9 | 1.8 | 22.8 | 480 | 1.20 | 87 | 110 |
3X35 | 0.9 | 1.8 | 25.0 | 580 | 0.868 | 105 | 130 |
3X50 | 1.0 | 1.8 | 24.4 | 670 | 0.641 | 130 | 160 |
3X70 | 1.1 | 1.9 | 29.4 | 910 | 0.443 | 165 | 195 |
3X95 | 1.1 | 2.0 | 33.6 | 1170 | 0.320 | 205 | 235 |
3X120 | 1.2 | 2.1 | 35.9 | 1460 | 0.253 | 240 | 265 |
3X150 | 1.4 | 2.3 | 39.9 | 1820 | 0.206 | 270 | 300 |
3X185 | 1.6 | 2.4 | 44.1 | 2200 | 0.164 | 315 | 340 |
3X240 | 1.7 | 2.6 | 51.1 | 2850 | 0.125 | 375 | 395 |
3X300 | 1.8 | 2.7 | 56.1 | 3500 | 0.100 | 435 | 445 |
3X400 | 2.0 | 3.0 | 62.4 | 4500 | 0.0778 | 510 | 510 |
0.6/1kV-4 core aluminum conductor XLPE insulated PVC sheathed power cable | |||||||
No. of cores and nominal cross section | Thickness of Insulation | Thickness of Sheath | Approx. overall Diameter | Approx. weight | Max. DC resistance of conductor(20℃) | Current carrying capacity | |
(mm2) | (mm) | (mm) | (mm) | (kg/km) | (Ω/km) | In Air(A) | In Ground(A) |
4X10 | 0.7 | 1.8 | 18.6 | 300 | 3.08 | 50 | 66 |
4X16 | 0.7 | 1.8 | 21.0 | 400 | 1.91 | 65 | 85 |
4X25 | 0.9 | 1.8 | 24.9 | 570 | 1.20 | 87 | 110 |
4X35 | 0.9 | 1.8 | 28.3 | 710 | 0.868 | 105 | 130 |
4X50 | 1.0 | 1.8 | 28.4 | 850 | 0.641 | 130 | 160 |
4X70 | 1.1 | 2.0 | 33.1 | 1160 | 0.443 | 165 | 195 |
4X95 | 1.1 | 2.1 | 37.1 | 1520 | 0.320 | 205 | 235 |
4X120 | 1.2 | 2.2 | 40.8 | 1898 | 0.253 | 240 | 265 |
4X150 | 1.4 | 2.4 | 45.2 | 2369 | 0.206 | 270 | 300 |
4X185 | 1.6 | 2.6 | 52.1 | 2925 | 0.164 | 315 | 340 |
4X240 | 1.7 | 2.8 | 57.8 | 3700 | 0.125 | 375 | 395 |
4X300 | 1.8 | 3.0 | 63.5 | 4580 | 0.100 | 435 | 445 |
4X400 | 2.0 | 3.3 | 70.9 | 5800 | 0.0778 | 510 | 510 |
0.6/1kV-5 core aluminum conductor XLPE insulated PVC sheathed power cable | |||||||
No. of cores and nominal cross section | Thickness of Insulation | Thickness of Sheath | Approx. overall Diameter | Approx. weight | Max. DC resistance of conductor(20℃) | Current carrying capacity | |
(mm2) | (mm) | (mm) | (mm) | (kg/km) | (Ω/km) | In Air(A) | In Ground(A) |
5X10 | 0.7 | 1.8 | 18.8 | 360 | 3.08 | 50 | 66 |
5X16 | 0.7 | 1.8 | 21.8 | 485 | 1.91 | 65 | 85 |
5X25 | 0.9 | 1.8 | 26.2 | 690 | 1.20 | 87 | 110 |
5X35 | 0.9 | 1.8 | 28.0 | 865 | 0.868 | 105 | 130 |
5X50 | 1.0 | 1.9 | 32.4 | 1138 | 0.641 | 130 | 160 |
5X70 | 1.1 | 2.1 | 37.4 | 1575 | 0.443 | 165 | 195 |
5X95 | 1.1 | 2.2 | 41.7 | 2068 | 0.320 | 205 | 235 |
5X120 | 1.2 | 2.4 | 46.2 | 2550 | 0.253 | 240 | 265 |
5X150 | 1.4 | 2.6 | 53.1 | 3165 | 0.206 | 270 | 300 |
5X185 | 1.6 | 2.8 | 58.9 | 3950 | 0.164 | 315 | 340 |
5X240 | 1.7 | 3.0 | 65.6 | 5025 | 0.125 | 375 | 395 |
5X300 | 1.8 | 3.2 | 72.0 | 6190 | 0.100 | 435 | 445 |