NA2XRY 0.6/1kV Aluminum Cable,AL/XLPE/SWA/PVC

Applications

The NA2XRH and NA2XRY are aluminium power cables with a voltage rating of 600/1000V designed to withstand harsh operating conditions and mechanical stresses. They are suitable for use in:

 Power and auxiliary fixed wiring cables

 Power networks

 Underground

 Outdoor and indoor devices

These power cables have a steel wire armour providing mechanical protection and making them suitable for underground installations.

For any more information or advice please contact the office on 0086-18832134509 (WhatsApp/WeChat)

Share:

Details

Overview

AL/XLPE/SWA/PVC Cable  

AL/XLPE/SWA/PVC Armoured Power Cables are the perfect choice when you need the toughest and most durable armoured cable for power distribution and transmission. Aluminium stranded conductors with a layer of steel wire armoured (SWA),  sheathed in polyethylene (XLPE) thermosetting insulation, and hard-wearing PVC(for the NA2XRY) or LSZH materials (for NA2XRH), these armoured cables can withstand twisting, crushing, impacts, temperature extremes, moisture, chemical hazards, and more. They're suitable for use in a range of environments, from industrial and manufacturing facilities to construction,which is used to connect equipment rated to 90℃. Where the cable is being used to connect equipment rated to 70℃, the NAYRY cable with PVC insulation may be considered.

The NA2XRH cables' halogen-free flame retardant outer sheath makes it suitable for installations in public places where in the event of fire there would be considerable risk to life and sensitive equipment. This range is widely used in public buildings such as hotels, schools, high constructions and hospitals. It is also used in refineries and data centers.  

Construction

 NA2XRY 0.6/1kV Aluminum Cable,AL/XLPE/SWA/PVC

Description: NA2XRY, XLPE Insulated Copper Power Cable   

Conductors: Class 1 or Class 2 of plain Aluminum,or of Class 5 of plain aluminum in accordance with IEC 60228.

Insulation: Cross-linked polyethylene XLPE

Insulation Colour: Natural or as required

Filler: Non-hygroscopic Material

Inner Sheath: Polyvinyl Chloride PVC

Reinforcement: Steel Wire

Outer Sheath: Extruded Polyvinyl Chloride PVC&Polyethylene PE&LSZH

Colour of Sheath: Black

Voltage Rating (Uo/U): 600/1000V         Test Voltage: 3.5kV for 5 minutes

Physical Properties

Maximal operating conductor Temperature: up to 70℃(PVC insulation); up to 90℃(XLPE insulation)

Operating Temperature Range: -5℃(PVC or LSZH sheath); -20℃(PE sheath)

Short Circuit Temperature(5 seconds maximum duration): 140℃-160℃(PVC insulation);250℃(XLPE insulation)

Technical Data

0.6/1kV-2 core aluminum conductor XLPE insulated steel wire armored PVC sheathed power cable
Nominal cross sectional areaInsulation thicknessSteel Wire diameterSheath thicknessApproximate outer diameterApprox.
weight
Max.D.C resistance of conductor(20℃)Current carrying capacity 
mm2mmmmmmmmkg/kmΩ/kmIn Air(A)In Ground(A)
2X2.50.70.81.814.833312.118 25 
2X40.70.81.815.73757.4124 33 
2X60.71.251.817.65704.6132 43 
2X100.71.251.820.16773.0841 55 
2X160.71.251.822.38081.9153 70 
2X250.91.61.826.311701.270 91 
2X350.91.61.827.612870.86884 109 
2X5011.61.930.815480.641105 130 
2X701.12235.421500.443133 158 
2X951.122.139.526000.32165 193 
2X1201.222.342.930030.253193 221 
2X1501.42.52.44839190.206221 245 
2X1851.62.52.652.745620.164256 277 









0.6/1kV-3 core aluminum conductor XLPE insulated steel wire armored PVC sheathed power cable
Nominal cross sectional areaInsulation thicknessSteel Wire diameterSheath thicknessApproximate outer diameterApprox.
weight
Max.D.C resistance of conductor(20℃)Current carrying capacity 
mm2mmmmmmmmkg/kmΩ/kmIn Air(A)In Ground(A)
3X2.50.70.81.815.335812.115 22 
3X40.70.81.816.24067.4120 28 
3X60.71.251.818.35844.6127 36 
3X100.71.251.820.97413.0835 46 
3X160.71.251.823.38911.9146 60 
3X250.91.61.827.612951.261 77 
3X350.91.61.82914650.86874 91 
3X5011.61.932.517650.64191 112
3X701.122.137.924880.443116 137 
3X951.122.241.829820.32144 165 
3X1201.222.345.534650.253168 186 
3X1501.42.52.551.346060.206189 210 
3X1851.62.52.755.953170.164221 238 
3X2401.72.52.962.164030.125263 277 
3X3001.82.5367.474300.1305 312 









0.6/1kV-4 core aluminum conductor XLPE insulated steel wire armored PVC sheathed power cable
Nominal cross sectional areaInsulation thicknessSteel Wire diameterSheath thicknessApproximate outer diameterApprox.
weight
Max.D.C resistance of conductor(20℃)Current carrying capacity 
mm2mmmmmmmmkg/kmΩ/kmIn Air(A)In Ground(A)
4X2.50.70.81.816.140912.115 22 
4X40.71.251.818.15777.4120 28 
4X60.71.251.819.36554.6127 36 
4X100.71.251.822.38383.0835 46 
4X160.71.61.825.711711.9146 60 
4X250.91.61.829.714821.261 77 
4X350.91.61.931.416920.86874 91
4X5011.6235.320620.64191112 
4X701.122.241.229180.443116 137 
4X951.122.345.635050.32144 165 
4X1201.22.52.551.246520.253168 186 
4X1501.42.52.756.154250.206189 210 
4X1851.62.52.861.363130.164221 238 
4X2401.72.53.168.176550.125263 277 
4X3001.82.53.274.189450.1305 312 









0.6/1kV-5 core aluminum conductor XLPE insulated steel wire armored PVC sheathed power cable
Nominal cross sectional areaInsulation thicknessSteel Wire diameterSheath thicknessApproximate outer diameterApprox.
weight
Max.D.C resistance of conductor(20℃)Current carrying capacity 
mm2mmmmmmmmkg/kmΩ/kmIn Air(A)In Ground(A)
5X2.50.71.251.817.956712.115 21.7
5X40.71.251.819.16457.4120 28
5X60.71.251.820.57364.6127 36.4
5X100.71.61.824.610983.0835 46.2
5X160.71.61.827.613111.9146 59.5
5X250.91.61.932.217081.261 77
5X350.91.6234.119550.86874 91
5X50122.239.727260.64191112
5X701.122.344.933760.443116 137 
5X951.12.52.551.346330.32144 165 
5X1201.22.52.755.953940.253168 186 
5X1501.42.52.861.463400.206189 210 
5X1851.62.5367.674880.164221 238 
5X2401.72.53.374.890380.125263 277 
5X3001.83.153.583.2116460.1305 312 



 


Contact Us Now