N2XBY CU/XLPE/STA/PVC 600/1000V Low power Cable

Applications

N2XBY cable is suitable for AC 50Hz power and distribution lines with rated voltage of 600/1000V, which can be used   

· in fixed industrial power applications

· Underground tunnels

· in power and switching stations

· local energy distributions

· industrial plants

Using steel tape armouring offers great mechanical protection, making it rigid with a large radius installation indoors and outdoors.

 For any more information or advice please contact the office on 0086-18832134509 (WhatsApp/WeChat)

Share:

Details

Overview

600/1000V,XLPE Insulated Cables, With steel tape armoured,PVC Sheath

0.6/1 KV CU/XPLE/STA/PVC cable plays a vital role in low-voltage power transmission and distribution, widely applied in building,industrial, and infrastructure settings to ensure the reliability and safety of power systems. This Power Cable with stranded compacted copper conductor is composed of copper conductor (CU), cross-linked polyethylene insulation (XPLE), steel tape armoring for mechanical protection and a polyvinyl chloride sheath (PVC). For fixed installation in interiors,outdoor installation,in soil,in water and concrete,if no posterior mechanical damage is to be expected.

Construction

N2XBY CU/XLPE/STA/PVC 600/1000V Low power Cable

Description: N2XBY, XLPE Insulated Copper Power Cable   

Conductors: Class 1 or Class 2 of plain copper,or of Class 5 of plain copper in accordance with IEC 60228.

Insulation: Cross-linked polyethylene XLPE

Insulation Colour: Natural or as required

Filler:  Non-hygroscopic Material

Inner Sheath:  Polyvinyl Chloride PVC

Reinforcement: Steel Tape
Outer Sheath: Extruded Polyvinyl Chloride PVC&Polyethylene PE&LSZH
Colour of Sheath:  Black
Voltage Rating (Uo/U): 600/1000V   
Test Voltage: 3.5kV for 5 minutes

Physical Properties

Maximal operating conductor Temperature: up to 70℃(PVC insulation); up to 90(XLPE insulation)

Operating Temperature Range: -5℃(PVC or LSZH sheath); -20℃(PE sheath)

Short Circuit Temperature(5 seconds maximum duration): 140-160℃(PVC insulation);250℃(XLPE insulation)

Technical Data

0.6/1kV-1 core copper conductor XLPE insulated with steel tape armouring and PVC sheathed power cable
No. of cores and nominal cross sectionThickness of InsulationNon-magnetic steel tape thicknessThickness of SheathApprox. overall DiameterApprox. weightMax. DC resistance of conductor(20℃)Current carrying capacity
(mm2)(mm)(mm)(mm)(mm)(kg/km)(Ω/km)In Air(A)In Ground(A)
1X100.7 0.2 1.4 10.2 244 1.837192
1X160.7 0.2 1.4 11.1 318 1.1592115
1X250.9 0.2 1.4 12.6 420 0.727120150
1X350.9 0.2 1.4 13.7 525 0.524150180
1X501.0 0.2 1.4 15.2 658 0.387180215
1X701.1 0.2 1.5 17.0 885 0.268230265
1X951.1 0.2 1.6 18.8 1154 0.193285320
1X1201.2 0.2 1.6 20.4 1404 0.153335360
1X1501.4 0.2 1.6 22.4 1698 0.124385410
1X1851.6 0.2 1.7 24.3 2075 0.0991450460
1X2401.7 0.2 1.8 26.9 2642 0.0754535535
1x3001.8 0.2 1.9 29.3 3250 0.0601620605
1x4002.0 0.2 2.0 33.0 4062 0.0470 720685