Contact
Applications
N2XBY cable is suitable for AC 50Hz power and distribution lines with rated voltage of 600/1000V, which can be used
· in fixed industrial power applications
· Underground tunnels
· in power and switching stations
· local energy distributions
· industrial plants
Using steel tape armouring offers great mechanical protection, making it rigid with a large radius installation indoors and outdoors.
For any more information or advice please contact the office on 0086-18832134509 (WhatsApp/WeChat)
Details
Description: N2XBY, XLPE Insulated Copper Power Cable
Conductors: Class 1 or Class 2 of plain copper,or of Class 5 of plain copper in accordance with IEC 60228.
Insulation: Cross-linked polyethylene XLPE
Insulation Colour: Natural or as required
Filler: Non-hygroscopic Material
Inner Sheath: Polyvinyl Chloride PVC
Physical Properties
Maximal operating conductor Temperature: up to 70℃(PVC insulation); up to 90℃(XLPE insulation)
Operating Temperature Range: -5℃(PVC or LSZH sheath); -20℃(PE sheath)
Short Circuit Temperature(5 seconds maximum duration): 140℃-160℃(PVC insulation);250℃(XLPE insulation)
Technical Data
0.6/1kV-2 core copper conductor XLPE insulated PVC sheathed power cable | ||||||||
No. of cores and nominal cross section | Thickness of Insulation | steel tape thickness | Thickness of Sheath | Approx. overall Diameter | Approx. weight | Max. DC resistance of conductor(20℃) | Current carrying capacity | |
(mm2) | (mm) | (mm) | (mm) | (mm) | (kg/km) | (Ω/km) | In Air(A) | In Ground(A) |
2X2.5 | 0.7 | 0.2 | 1.8 | 12.4 | 230 | 7.41 | 33 | 46 |
2X4 | 0.7 | 0.2 | 1.8 | 13.4 | 277 | 4.61 | 43 | 59 |
2X6 | 0.7 | 0.2 | 1.8 | 14.4 | 336 | 3.08 | 55 | 75 |
2X10 | 0.7 | 0.2 | 1.8 | 16.0 | 452 | 1.83 | 76 | 100 |
2X16 | 0.7 | 0.2 | 1.8 | 17.8 | 609 | 1.15 | 97 | 130 |
2X25 | 0.9 | 0.2 | 1.8 | 20.8 | 845 | 0.727 | 130 | 165 |
2X35 | 0.9 | 0.2 | 1.8 | 23.0 | 1065 | 0.524 | 160 | 200 |
2X50 | 1.0 | 0.2 | 1.8 | 26.0 | 1297 | 0.387 | 195 | 240 |
2X70 | 1.1 | 0.2 | 1.9 | 29.4 | 1775 | 0.268 | 245 | 290 |
2X95 | 1.1 | 0.2 | 2.1 | 32.8 | 2340 | 0.193 | 305 | 355 |
2X120 | 1.2 | 0.5 | 2.2 | 37.9 | 3238 | 0.153 | 355 | 405 |
2X150 | 1.4 | 0.5 | 2.3 | 41.7 | 3971 | 0.124 | 405 | 450 |
2X185 | 1.6 | 0.5 | 2.4 | 45.7 | 4845 | 0.0991 | 465 | 510 |
0.6/1kV-3 core copper conductor XLPE insulated PVC sheathed power cable | ||||||||
No. of cores and nominal cross section | Thickness of Insulation | steel tape thickness | Thickness of Sheath | Approx. overall Diameter | Approx. weight | Max. DC resistance of conductor(20℃) | Current carrying capacity | |
(mm2) | (mm) | (mm) | (mm) | (mm) | (kg/km) | (Ω/km) | In Air(A) | In Ground(A) |
3X2.5 | 0.7 | 0.2 | 1.8 | 12.9 | 265 | 7.41 | 28 | 39 |
3X4 | 0.7 | 0.2 | 1.8 | 14.0 | 328 | 4.61 | 37 | 51 |
3X6 | 0.7 | 0.2 | 1.8 | 15.1 | 410 | 3.08 | 47 | 64 |
3X10 | 0.7 | 0.2 | 1.8 | 16.8 | 560 | 1.83 | 65 | 86 |
3X16 | 0.7 | 0.2 | 1.8 | 18.7 | 775 | 1.15 | 84 | 110 |
3X25 | 0.9 | 0.2 | 1.8 | 22.0 | 1098 | 0.727 | 110 | 140 |
3X35 | 0.9 | 0.2 | 1.8 | 24.4 | 1410 | 0.524 | 135 | 170 |
3X50 | 1.0 | 0.2 | 1.8 | 27.6 | 1780 | 0.387 | 170 | 205 |
3X70 | 1.1 | 0.2 | 2.0 | 31.5 | 2475 | 0.268 | 215 | 250 |
3X95 | 1.1 | 0.5 | 2.1 | 36.8 | 3260 | 0.193 | 265 | 300 |
3X120 | 1.2 | 0.5 | 2.2 | 40.5 | 4477 | 0.153 | 310 | 345 |
3X150 | 1.4 | 0.5 | 2.3 | 44.6 | 5440 | 0.124 | 350 | 385 |
3X185 | 1.6 | 0.5 | 2.4 | 49.1 | 6707 | 0.0991 | 405 | 435 |
3X240 | 1.7 | 0.5 | 2.6 | 54.8 | 8533 | 0.0754 | 480 | 500 |
3X300 | 1.8 | 0.5 | 2.7 | 60.0 | 10455 | 0.0601 | 555 | 565 |
0.6/1kV-4 core copper conductor XLPE insulated PVC sheathed power cable | ||||||||
No. of cores and nominal cross section | Thickness of Insulation | steel tape thickness | Thickness of Sheath | Approx. overall Diameter | Approx. weight | Max. DC resistance of conductor(20℃) | Current carrying capacity | |
(mm2) | (mm) | (mm) | (mm) | (mm) | (kg/km) | (Ω/km) | In Air(A) | In Ground(A) |
4X2.5 | 0.7 | 0.2 | 1.8 | 13.7 | 308 | 7.41 | 28 | 39 |
4X4 | 0.7 | 0.2 | 1.8 | 15.0 | 388 | 4.61 | 37 | 51 |
4X6 | 0.7 | 0.2 | 1.8 | 16.2 | 488 | 3.08 | 47 | 64 |
4X10 | 0.7 | 0.2 | 1.8 | 18.1 | 681 | 1.83 | 65 | 86 |
4X16 | 0.7 | 0.2 | 1.8 | 20.3 | 960 | 1.15 | 84 | 110 |
4X25 | 0.9 | 0.2 | 1.8 | 23.9 | 1375 | 0.727 | 110 | 140 |
4X35 | 0.9 | 0.2 | 1.8 | 26.6 | 1779 | 0.524 | 135 | 170 |
4X50 | 1.0 | 0.2 | 1.9 | 30.4 | 2296 | 0.387 | 170 | 205 |
4X70 | 1.1 | 0.2 | 2.1 | 34.7 | 3175 | 0.268 | 215 | 250 |
4X95 | 1.1 | 0.5 | 2.3 | 40.4 | 4665 | 0.193 | 265 | 300 |
4X120 | 1.2 | 0.5 | 2.4 | 44.5 | 5728 | 0.153 | 310 | 345 |
4X150 | 1.4 | 0.5 | 2.6 | 49.7 | 6999 | 0.124 | 350 | 385 |
4X185 | 1.6 | 0.5 | 2.7 | 54.5 | 8657 | 0.0991 | 405 | 435 |
4X240 | 1.7 | 0.5 | 2.9 | 60.7 | 11000 | 0.0754 | 480 | 500 |
4X300 | 1.8 | 0.5 | 3.1 | 66.4 | 13587 | 0.0601 | 555 | 565 |
0.6/1kV-5 core copper conductor XLPE insulated PVC sheathed power cable | ||||||||
No. of cores and nominal cross section | Thickness of Insulation | steel tape thickness | Thickness of Sheath | Approx. overall Diameter | Approx. weight | Max. DC resistance of conductor(20℃) | Current carrying capacity | |
(mm2) | (mm) | (mm) | (mm) | (mm) | (kg/km) | (Ω/km) | In Air(A) | In Ground(A) |
5X2.5 | 0.7 | 0.2 | 1.8 | 15.6 | 350 | 7.41 | 28 | 39 |
5X4 | 0.7 | 0.2 | 1.8 | 16.8 | 447 | 4.61 | 37 | 51 |
5X6 | 0.7 | 0.2 | 1.8 | 18.2 | 569 | 3.08 | 47 | 64 |
5X10 | 0.7 | 0.2 | 1.8 | 21.6 | 805 | 1.83 | 65 | 86 |
5X16 | 0.7 | 0.2 | 1.8 | 24.6 | 1150 | 1.15 | 84 | 110 |
5X25 | 0.9 | 0.2 | 1.8 | 29.0 | 1655 | 0.727 | 110 | 140 |
5X35 | 0.9 | 0.2 | 1.9 | 31.0 | 2166 | 0.524 | 135 | 170 |
5X50 | 1.0 | 0.2 | 2.1 | 35.7 | 2945 | 0.387 | 170 | 205 |
5X70 | 1.1 | 0.5 | 2.3 | 42.4 | 4453 | 0.268 | 215 | 250 |
5X95 | 1.1 | 0.5 | 2.4 | 47.2 | 5862 | 0.193 | 265 | 300 |
5X120 | 1.2 | 0.5 | 2.6 | 51.8 | 7176 | 0.153 | 310 | 345 |
5X150 | 1.4 | 0.5 | 2.7 | 57.6 | 8770 | 0.124 | 350 | 385 |
5X185 | 1.6 | 0.5 | 2.9 | 63.8 | 10827 | 0.0991 | 405 | 435 |
5X240 | 1.7 | 0.5 | 3.2 | 70.7 | 13770 | 0.0754 | 480 | 500 |
5X300 | 1.8 | 0.5 | 3.4 | 78.0 | 16960 | 0.0601 | 555 | 565 |