Contact
Applications
N2XBY cables are designed for local distribution systems and for delivering power and auxiliary control in the Building and Construction industry with a voltage rating of 0.6/1kV, which can be used
● in fixed industrial power applications
● underground tunnels
● in power and switching stations
● local energy distributions
● industrial plants
Using steel tape armouring offers great mechanical protection, making it rigid with a large radius installation indoors and outdoors.
For any more information or advice please contact the office on 0086-18832134509 (WhatsApp/WeChat)
Details
600/1000V,XLPE Insulated Cables, With steel tape armoured,PVC Sheath
N2XBY cables are designed for local distribution systems and for delivering power and auxiliary control in the building and construction industry with a voltage rating of 0.6/1kV.The N2XBY is resistant to mechanical stresses as a result of the double layer of galvanized steel tape armour applied to the cable. The STA provides improved flexibility compared to round steel wires or other more rigid armouring.
With a flame retardant PVC outer sheath, the N2XBY cable is suitable for fixed installations internally. The UV resistance makes external applications also permissible. 0.6/1 KV CU/XPLE/STA/PVC cable plays a vital role in low-voltage power transmission and distribution, widely applied in building,industrial, and infrastructure settings to ensure the reliability and safety of power systems. This Power Cable with stranded compacted copper conductor is composed of copper conductor (CU), cross-linked polyethylene insulation (XPLE), steel tape armoring for mechanical protection and a polyvinyl chloride sheath (PVC). For used in electric power plants, transformer stations, industrial plants, metropolitan networks and other electric plants. Applied in conditions requiring protection against heavier mechanical damages, but where cables are not exposed to heavier tensile strain.
Construction
Description: N2XBY, XLPE Insulated Copper Power Cable
Conductors: Class 1 or Class 2 of plain copper,or of Class 5 of plain copper in accordance with IEC 60228.
Insulation: Cross-linked polyethylene XLPE
Insulation Colour: Natural or as required
Filler: Non-hygroscopic Material
Inner Sheath: Polyvinyl Chloride PVC
Reinforcement: Steel Tape
Outer Sheath: Extruded Polyvinyl Chloride PVC&Polyethylene PE&LSZH
Colour of Sheath: Black
Voltage Rating (Uo/U): 600/1000V Test Voltage: 3.5kV for 5 minutes
Physical Properties
Maximal operating conductor Temperature: up to 70℃(PVC insulation); up to 90℃(XLPE insulation)
Operating Temperature Range: -5℃(PVC or LSZH sheath); -20℃(PE sheath)
Short Circuit Temperature(5 seconds maximum duration): 140℃-160℃(PVC insulation);250℃(XLPE insulation)
Technical Data
0.6/1kV-2 core copper conductor XLPE insulated PVC sheathed power cable | ||||||||
No. of cores and nominal cross section | Thickness of Insulation | steel tape thickness | Thickness of Sheath | Approx. overall Diameter | Approx. weight | Max. DC resistance of conductor(20℃) | Current carrying capacity | |
(mm2) | (mm) | (mm) | (mm) | (mm) | (kg/km) | (Ω/km) | In Air(A) | In Ground(A) |
2X2.5 | 0.7 | 0.2 | 1.8 | 12.4 | 230 | 7.41 | 33 | 46 |
2X4 | 0.7 | 0.2 | 1.8 | 13.4 | 277 | 4.61 | 43 | 59 |
2X6 | 0.7 | 0.2 | 1.8 | 14.4 | 336 | 3.08 | 55 | 75 |
2X10 | 0.7 | 0.2 | 1.8 | 16.0 | 452 | 1.83 | 76 | 100 |
2X16 | 0.7 | 0.2 | 1.8 | 17.8 | 609 | 1.15 | 97 | 130 |
2X25 | 0.9 | 0.2 | 1.8 | 20.8 | 845 | 0.727 | 130 | 165 |
2X35 | 0.9 | 0.2 | 1.8 | 23.0 | 1065 | 0.524 | 160 | 200 |
2X50 | 1.0 | 0.2 | 1.8 | 26.0 | 1297 | 0.387 | 195 | 240 |
2X70 | 1.1 | 0.2 | 1.9 | 29.4 | 1775 | 0.268 | 245 | 290 |
2X95 | 1.1 | 0.2 | 2.1 | 32.8 | 2340 | 0.193 | 305 | 355 |
2X120 | 1.2 | 0.5 | 2.2 | 37.9 | 3238 | 0.153 | 355 | 405 |
2X150 | 1.4 | 0.5 | 2.3 | 41.7 | 3971 | 0.124 | 405 | 450 |
2X185 | 1.6 | 0.5 | 2.4 | 45.7 | 4845 | 0.0991 | 465 | 510 |
0.6/1kV-3 core copper conductor XLPE insulated PVC sheathed power cable | ||||||||
No. of cores and nominal cross section | Thickness of Insulation | steel tape thickness | Thickness of Sheath | Approx. overall Diameter | Approx. weight | Max. DC resistance of conductor(20℃) | Current carrying capacity | |
(mm2) | (mm) | (mm) | (mm) | (mm) | (kg/km) | (Ω/km) | In Air(A) | In Ground(A) |
3X2.5 | 0.7 | 0.2 | 1.8 | 12.9 | 265 | 7.41 | 28 | 39 |
3X4 | 0.7 | 0.2 | 1.8 | 14.0 | 328 | 4.61 | 37 | 51 |
3X6 | 0.7 | 0.2 | 1.8 | 15.1 | 410 | 3.08 | 47 | 64 |
3X10 | 0.7 | 0.2 | 1.8 | 16.8 | 560 | 1.83 | 65 | 86 |
3X16 | 0.7 | 0.2 | 1.8 | 18.7 | 775 | 1.15 | 84 | 110 |
3X25 | 0.9 | 0.2 | 1.8 | 22.0 | 1098 | 0.727 | 110 | 140 |
3X35 | 0.9 | 0.2 | 1.8 | 24.4 | 1410 | 0.524 | 135 | 170 |
3X50 | 1.0 | 0.2 | 1.8 | 27.6 | 1780 | 0.387 | 170 | 205 |
3X70 | 1.1 | 0.2 | 2.0 | 31.5 | 2475 | 0.268 | 215 | 250 |
3X95 | 1.1 | 0.5 | 2.1 | 36.8 | 3260 | 0.193 | 265 | 300 |
3X120 | 1.2 | 0.5 | 2.2 | 40.5 | 4477 | 0.153 | 310 | 345 |
3X150 | 1.4 | 0.5 | 2.3 | 44.6 | 5440 | 0.124 | 350 | 385 |
3X185 | 1.6 | 0.5 | 2.4 | 49.1 | 6707 | 0.0991 | 405 | 435 |
3X240 | 1.7 | 0.5 | 2.6 | 54.8 | 8533 | 0.0754 | 480 | 500 |
3X300 | 1.8 | 0.5 | 2.7 | 60.0 | 10455 | 0.0601 | 555 | 565 |
0.6/1kV-4 core copper conductor XLPE insulated PVC sheathed power cable | ||||||||
No. of cores and nominal cross section | Thickness of Insulation | steel tape thickness | Thickness of Sheath | Approx. overall Diameter | Approx. weight | Max. DC resistance of conductor(20℃) | Current carrying capacity | |
(mm2) | (mm) | (mm) | (mm) | (mm) | (kg/km) | (Ω/km) | In Air(A) | In Ground(A) |
4X2.5 | 0.7 | 0.2 | 1.8 | 13.7 | 308 | 7.41 | 28 | 39 |
4X4 | 0.7 | 0.2 | 1.8 | 15.0 | 388 | 4.61 | 37 | 51 |
4X6 | 0.7 | 0.2 | 1.8 | 16.2 | 488 | 3.08 | 47 | 64 |
4X10 | 0.7 | 0.2 | 1.8 | 18.1 | 681 | 1.83 | 65 | 86 |
4X16 | 0.7 | 0.2 | 1.8 | 20.3 | 960 | 1.15 | 84 | 110 |
4X25 | 0.9 | 0.2 | 1.8 | 23.9 | 1375 | 0.727 | 110 | 140 |
4X35 | 0.9 | 0.2 | 1.8 | 26.6 | 1779 | 0.524 | 135 | 170 |
4X50 | 1.0 | 0.2 | 1.9 | 30.4 | 2296 | 0.387 | 170 | 205 |
4X70 | 1.1 | 0.2 | 2.1 | 34.7 | 3175 | 0.268 | 215 | 250 |
4X95 | 1.1 | 0.5 | 2.3 | 40.4 | 4665 | 0.193 | 265 | 300 |
4X120 | 1.2 | 0.5 | 2.4 | 44.5 | 5728 | 0.153 | 310 | 345 |
4X150 | 1.4 | 0.5 | 2.6 | 49.7 | 6999 | 0.124 | 350 | 385 |
4X185 | 1.6 | 0.5 | 2.7 | 54.5 | 8657 | 0.0991 | 405 | 435 |
4X240 | 1.7 | 0.5 | 2.9 | 60.7 | 11000 | 0.0754 | 480 | 500 |
4X300 | 1.8 | 0.5 | 3.1 | 66.4 | 13587 | 0.0601 | 555 | 565 |
0.6/1kV-5 core copper conductor XLPE insulated PVC sheathed power cable | ||||||||
No. of cores and nominal cross section | Thickness of Insulation | steel tape thickness | Thickness of Sheath | Approx. overall Diameter | Approx. weight | Max. DC resistance of conductor(20℃) | Current carrying capacity | |
(mm2) | (mm) | (mm) | (mm) | (mm) | (kg/km) | (Ω/km) | In Air(A) | In Ground(A) |
5X2.5 | 0.7 | 0.2 | 1.8 | 15.6 | 350 | 7.41 | 28 | 39 |
5X4 | 0.7 | 0.2 | 1.8 | 16.8 | 447 | 4.61 | 37 | 51 |
5X6 | 0.7 | 0.2 | 1.8 | 18.2 | 569 | 3.08 | 47 | 64 |
5X10 | 0.7 | 0.2 | 1.8 | 21.6 | 805 | 1.83 | 65 | 86 |
5X16 | 0.7 | 0.2 | 1.8 | 24.6 | 1150 | 1.15 | 84 | 110 |
5X25 | 0.9 | 0.2 | 1.8 | 29.0 | 1655 | 0.727 | 110 | 140 |
5X35 | 0.9 | 0.2 | 1.9 | 31.0 | 2166 | 0.524 | 135 | 170 |
5X50 | 1.0 | 0.2 | 2.1 | 35.7 | 2945 | 0.387 | 170 | 205 |
5X70 | 1.1 | 0.5 | 2.3 | 42.4 | 4453 | 0.268 | 215 | 250 |
5X95 | 1.1 | 0.5 | 2.4 | 47.2 | 5862 | 0.193 | 265 | 300 |
5X120 | 1.2 | 0.5 | 2.6 | 51.8 | 7176 | 0.153 | 310 | 345 |
5X150 | 1.4 | 0.5 | 2.7 | 57.6 | 8770 | 0.124 | 350 | 385 |
5X185 | 1.6 | 0.5 | 2.9 | 63.8 | 10827 | 0.0991 | 405 | 435 |
5X240 | 1.7 | 0.5 | 3.2 | 70.7 | 13770 | 0.0754 | 480 | 500 |
5X300 | 1.8 | 0.5 | 3.4 | 78.0 | 16960 | 0.0601 | 555 | 565 |