N2XY(U-1000 R2V RVFV) XLPE Insulated copper cable, low voltage,CU/XLPE/PVC

Applications

N2XY cables(U-1000 R2V RVFV) are used for electricity supply in low voltage installation system,they are suitable for: 

· installation in indoors and outdoors 

· in cable ducts

· under ground

· in power and switching stations

· local energy distributions

· industrial plants

where there is no risk of mechanical damage.

 

 For any more information or advice please contact the office on 0086-18832134509(WhatsApp/WeChat)


Share:

Details

Overview

XLPE Insulated,PVC Sheathed Cable,0.6/1kV

The 0.6/1 KV CU/XPLE/PVC cable(U-1000 R2V RVFV) plays a vital role in low-voltage power transmission and distribution, widely applied in building,industrial, and infrastructure settings to ensure the reliability and safety of power systems. This Power Cable with stranded compacted copper conductor is composed of copper conductor (CU), cross-linked polyethylene insulation (XPLE), and a polyvinyl chloride sheath (PVC). For fixed installation in interiors,outdoor installation,in soil,in water and concrete,if no posterior mechanical damage is to be expected.

Construction

N2XY XLPE Insulated copper cable, low voltage,CU/XLPE/PVCDescription: N2XY, XLPE Insulated Copper Power Cable   

Conductors:Class 1 or Class 2 of plain copper,or of Class 5 of plain copper in accordance with IEC 60228.

Insulation:Cross-linked polyethylene XLPE

Insulation Colour:Natural or as required

Filler:  Non-hygroscopic Material

Outer Sheath:Extruded Polyvinyl Chloride PVC&Polyethylene PE&LSZH

Colour of Sheath:  Black

Voltage Rating (Uo/U):600/1000V   

Test Voltage:  3.5kV for 5 minutes

Physical Properties

Maximal operating conductor Temperature: up to 70℃(PVC insulation); up to 90(XLPE insulation)

Operating Temperature Range: -5℃(PVC or LSZH sheath); -20℃(PE sheath)

Short Circuit Temperature(5 seconds maximum duration): 140-160℃(PVC insulation);250℃(XLPE insulation)

Technical Data

0.6/1kV-1 core copper conductor XLPE insulated PVC sheathed power cable
No. of cores and nominal cross sectionThickness of Insulation Thickness of SheathApprox. overall DiameterApprox. weightMax. DC resistance of conductor(20℃)Current carrying capacity
(mm2)(mm)(mm)(mm)(kg/km)(Ω/km)In Air(A)In Ground(A)
1X1.50.7 1.4 5.5 4812.12332
1X2.50.7 1.4 5.9 597.413142
1X40.7 1.4 6.4 754.614155
1X60.7 1.4 6.9 953.085269
1X100.7 1.4 8.0 1401.837192
1X160.7 1.4 9.0 2001.1592115
1X250.9 1.4 10.6 3100.727120150
1X350.9 1.4 11.6 4100.524150180
1X501.0 1.4 13.1 5100.387180215
1X701.1 1.4 15.0 7100.268230265
1X951.1 1.5 16.8 9900.193285320
1X1201.2 1.5 18.4 12300.153335360
1X1501.4 1.6 20.5 14500.124385410
1X1851.6 1.6 22.6 18000.0991450460
1X2401.7 1.7 25.2 23000.0754535535
1x3001.8 1.8 27.8 29600.0601620605
1x4002.0 1.9 31.4 38000.0470 720685
1x5002.2 2.0 34.9 48000.0366835775
1X6302.4 2.2 39.1 61000.0283960865


Contact Us Now