18/30KV N2XSY Power Cable

Applications

N2XSY is a single core cable with a stranded copper conductor, XLPE insulation, copper wire screen with intermittent copper tape screen and PVC oversheath. If using PE oversheath, that is N2XS2Y. The cables are mainly used for: 

 Indoors and in cable ducts

 Outdoors,underground 

 In power supply stations

 Transformer stations

 Industrial Plants

Due to the good laying characteristic, this cable can also be installed in difficult line guideways.

The inner conducting layer between the conductor and the XLPE insulation and the firmly bonded outer conducting layer on the XLPE insulation assures a construction free of partial discharges with high operational reliabilities.

For any more information or advice please contact the office on 0086-18832134509 (WhatsApp/WeChat)

Share:

Details

Overview

CU/XLPE/CWS/PVC Cable

 The N2XSY (medium cable)has a single core copper stranded class 2 conductor with cross-linked polyethylene(XLPE)insulation, copper wire screen with intermittent copper tape screen and PVC oversheath. If using PE oversheath, that is N2XS2Y. N2XSY cable is widely used for power distribution networks, transformer stations, switching blocks and power plants, including in the renewable energy sector, the N2XSY offers a low factor of dielectric loss and excellent insulation property of XLPE for high operational reliability. It should not be subjected to heavy mechanical or tensile strain. It can be manipulated and installed in ambient temperatures ranging between -5℃ and +70℃.

Construction 

18/30KV N2XSY Power Cable

Descriptions:N2XSY Single Core MV Power Cable

Conductor:Copper, Class2,Circular compacted conductors

Conductor Screen: Non-metallic,semi-conducting compound

Insulation: Cross-linked polyethylene XLPE

Insulation Screen: Non-metallic,semi-conducting compound

Metallic Screen: Copper wire screen with intermittent copper tape screen

Outer Sheath: Polyvinyl Chloride PVC

Physical Properties

Operating Temperature: up to 70℃(PVC insulation); up to 90℃(XLPE insulation)

Temperature Range: -5℃(PVC or LSZH sheath); -20℃(PE sheath)

Short Circuit Temperature(5 seconds maximum duration): 140℃-160℃(PVC insulation);250℃(XLPE insulation)

Nominal Voltages:U0/U 6/10 kV, 12/20 kV, 18/30 kV

Technical Data 

                                                        Single Core Cable(N2XSY)-6/10KV 
No. of cores and nominal cross sectionCopper Wire ScreenThickness of InsulationThickness of sheathApprox. Overall Diameter (min-max)Approx. WeightMax. DC Resistance of conductor(20℃)Current Carrying Capacity
mm²mm²mmmmmmkg/kmΩ/kmin air(A)in ground(A)
1x35163.41.823-289050.524182161
1x50163.41.824-2910800.387215188
1x70163.41.826-3113100.268267230
1x95163.41.826-3215800.193325274
1x120163.41.828-3418600.153375310
1x150163.41.829-3520400.124421342
1x150253.41.829-3522100.124421342
1x185163.41.931-3724500.0991480384
1x185253.41.931-3725800.0991480384
1x240163.42.0 33-3930000.0754564441
1x240253.42.0 33-3931300.0754564441
1x300253.42.0 36-4137800.060 645495
1x400353.42.140-4546700.047717531
1x500353.42.243-4857500.0366811585
1x630353.42.344-4971800.0283913641
                                                   Single Core Cable(N2XSY)-18/30KV
No. of cores and nominal cross sectionCopper Wire ScreenThickness of InsulationThickness of sheathApprox. Overall Diameter (min-max)Approx. WeightMax. DC Resistance of conductor(20℃)Current Carrying Capacity
mm2mm²mmmmmmkg/kmΩ/kmin air(A)in ground(A)
1x50168.01.932-3814800.387215188
1x70168.02.034-4017300.268267230
1x95168.02.135-4120600.193325274
1x120168.02.1 37-4323300.153375310
1x150258.02.1 38-4427200.124421342
1x185258.02.2 40-4631000.0991480384
1x240258.02.3 42-4837300.0754564441
1x300258.02.3 45-5140000.060 645495
1x400358.02.548-5453300.047717531
1x500358.02.551-5764800.0366811585
1x630358.0 2.752-5979700.0283913641


Contact Us Now