NA2XSY Single Core Cable

Applications

The NA2XSY (medium voltage)has a single core aluminium stranded class 2 conductor with cross-linked polyethylene (XLPE) insulation, copper tape metallic screen, and polyvinyl chloride (PVC) oversheath.They are mainly used for: 

Indoors and in cable ducts

Outdoors,underground 

In power supply stations

Transformer stations

Industrial Plants

Due to the good laying characteristic, this cable can also be installed in difficult line guideways.

The inner conducting layer between the conductor and the XLPE insulation and the firmly bonded outer conducting layer on the XLPE insulation assures a construction free of partial discharges with high operational reliabilities.

 For any more information or advice,please contact the office on 0086-18832134509(WhatsApp/WeChat)

Share:

Details

Overview

AL/XLPE/CTS/PVC Cable

The NA2XSY (medium voltage)has a single core aluminium stranded class 2 conductor with cross-linked polyethylene (XLPE) insulation, copper tape metallic screen, and polyvinyl chloride (PVC) oversheath. NA2XSY cable is widely used in internal/external power distribution networks,external where it's either direct buried or installed into cable ducting, but also it can be run and terminated inside a building as the NA2XSY cable is flame retardant.

The NA2XSY provides long-term operational reliability due to a low dielectric loss factor and excellent insulation property of XLPE, which makes it widely used in transformer stations, electric power plants and industrial plants. Nevertheless, it should be used in fixed installations to avoid mechanical or tensile strain.

Construction 

 NA2XSY Single Core Cable

Descriptions:NA2XSY Single Core MV Power Cable

Conductor:Aluminum, Class2,Circular compacted conductors

Conductor Screen: Non-metallic,semi-conducting compound

Insulation: Cross-linked polyethylene XLPE

Insulation Screen: Non-metallic,semi-conducting compound

Metallic Screen: Copper Tape

Outer Sheath: Polyvinyl Chloride PVC&Polyethylene PE&LSZH


Physical Properties

Operating Temperature: up to 70℃(PVC insulation); up to 90℃(XLPE insulation)

Temperature Range: -5℃(PVC or LSZH sheath); -20℃(PE sheath)

Short Circuit Temperature(5 seconds maximum duration): 140℃-160℃(PVC insulation);250℃(XLPE insulation)


Nominal Voltages:U0/U 6/10 kV, 12/20 kV, 18/30 kV

Technical Data

Single Core Cable(NA2XSY)-6/10KV 
No. of cores and nominal cross sectionThickness of InsulationThickness of sheathApprox. Overall DiameterApprox. WeightMax. DC Resistance of conductor(20℃)Current Carrying Capacity
mm2mmmmmmkg/kmΩ/kmin air(A)in ground(A)
1x163.41.818.53901.9185115
1x253.41.819.54421.2130145
1x353.41.820.54960.868160175
1x503.41.821.85640.641190210
1x703.41.823.56670.443240260
1x953.41.825.17810.32295315
1x1203.41.826.58850.253340360
1x1503.41.828.0 9970.206385405
1x1853.41.929.911580.164440455
1x2403.42.0 32.313850.125530535
1x3003.42.0 34.516080.100 605605
1x4003.42.137.719320.0778715705
1x5003.42.240.823300.0605835805
1x6303.42.344.828380.0469930920
Single Core Cable(NA2XSY)-8.7/15KV
No. of cores and nominal cross sectionThickness of InsulationThickness of sheathApprox. Overall DiameterApprox. WeightMax. DC Resistance of conductor(20℃)Current Carrying Capacity
mm2mmmmmmkg/kmΩ/kmin air(A)in ground(A)
1x254.51.821.75251.2130145
1x354.51.822.75820.868160175
1x504.51.824.06550.641190210
1x704.51.825.77630.443240260
1x954.51.827.38820.32295315
1x1204.51.928.910040.253340360
1x1504.51.930.4 11220.206385405
1x1854.52.0 32.312900.164440455
1x2404.52.0 34.515110.125530535
1x3004.52.1 36.917570.100 605605
1x4004.52.240.120940.0778715705
1x5004.52.343.225040.0605835805
1x6304.52.447.230270.0469930920
Single Core Cable(NA2XSY)-12/20KV
No. of cores and nominal cross sectionThickness of InsulationThickness of sheathApprox. Overall DiameterApprox. WeightMax. DC Resistance of conductor(20℃)Current Carrying Capacity
mm2mmmmmmkg/kmΩ/kmin air(A)in ground(A)
1x355.51.825.466750.868115175
1x505.51.826.767640.641140210
1x705.51.828.468770.443170255
1x955.51.930.2610130.32205310
1x1205.52.0 31.6611300.253240345
1x1505.52.0 33.5 12820.206270400
1x1855.52.1 35.0614340.164310455
1x2405.52.1 37.6616850.125360530
1x3005.52.2 39.8619380.100 420605
1x4005.52.343.2623460.0778485700
1x5005.52.447.1428020.0605535795
Single Core Cable(NA2XSY)-18/30KV,19/33KV
No. of cores and nominal cross sectionThickness of InsulationThickness of sheathApprox. Overall DiameterApprox. WeightMax. DC Resistance of conductor(20℃)Current Carrying Capacity
mm2mmmmmmkg/kmΩ/kmin air(A)in ground(A)
1x358.01.930.19230.868185134
1x508.02.031.310090.641222157
1x708.02.033.211490.443278192
1x958.02.13513010.32338229
1x1208.02.1 36.414300.253391260
1x1508.02.2 37.9 15730.206440288
1x1858.02.2 39.717440.164504324
1x2408.02.3 42.320120.125593373
1x3008.02.4 44.622810.100 677419
1x4008.02.547.526470.0778769466
1x5008.02.650.931010.0605872573