Contact
Applications
NA2XSEY cables are three-core class 2 stranded aluminium medium voltage cables, the cables are mainly used for:
● Indoors and in cable ducts
● Outdoors,underground
● In power supply stations
● Transformer stations
● Industrial Plants
Due to the good laying characteristic, this cable can also be installed in difficult line guideways.
The inner conducting layer between the conductor and the XLPE insulation and the firmly bonded outer conducting layer on the XLPE insulation assures a construction free of partial discharges with high operational reliabilities.
For any more information or advice please contact the office on 0086-18832134509 (WhatsApp/WeChat)
Details
AL/XLPE/CTS/PVC Cable
NA2XSEY cables are three-core class 2 stranded aluminium medium voltage cables, they are the three-core variants of the cable NA2XSY where the 'E' in the designation refers to each of the three cores being individually screened. NA2XSEY have a cross-linked polyethylene (XLPE) insulation, copper tape screen, and a polyvinyl chloride (PVC) oversheath.The inner conducting layer between the conductor and the XLPE insulation and the firmly bonded outer conducting layer on the XLPE insulation assures a construction free of partial discharges with high operational reliabilities.
The NA2XSEY offers a low factor of dielectric loss and excellent insulation property of XLPE for high operational reliability, which makes the NA2XSEY cables are widely used in the building and construction, renewable energy, and power transmission industries where the cables can be laid directly into the ground or cable ducts.
Construction
Descriptions:NA2XSEY Three Core MV Power Cable
Conductor:Aluminum, Class2,Circular compacted conductors
Conductor Screen: Non-metallic,semi-conducting compound
Insulation: Cross-linked polyethylene XLPE
Insulation Screen: Non-metallic,semi-conducting compound
Metallic Screen: Copper Tape
Filler: Non-hygroscopic Material
Binder Tape: Non-hygroscopic Material
Outer Sheath: Polyvinyl Chloride PVC&Polyethylene PE&LSZH
Physical Properties
Operating Temperature: up to 70℃(PVC insulation); up to 90℃(XLPE insulation)
Temperature Range: -5℃(PVC or LSZH sheath); -20℃(PE sheath)
Short Circuit Temperature(5 seconds maximum duration): 140℃-160℃(PVC insulation);250℃(XLPE insulation)
Nominal Voltages:U0/U 1.8/3kV , 6/10 kV, 12/20 kV, 18/30 kV
Technical Data
Three Core Cable(NA2XSEY)-6/10KV | |||||||
No. of cores and nominal cross section | Thickness of Insulation | Thickness of sheath | Approx. Overall Diameter | Approx. Weight | Max. DC Resistance of conductor(20℃) | Current Carrying Capacity | |
mm2 | mm | mm | mm | kg/km | Ω/km | in air(A) | in ground(A) |
3Cx70 | 3.4 | 2.5 | 53 | 2750 | 0.443 | 183 | 174 |
3Cx95 | 3.4 | 2.7 | 58 | 3400 | 0.32 | 222 | 208 |
3Cx120 | 3.4 | 2.7 | 61 | 3700 | 0.253 | 255 | 236 |
3Cx150 | 3.4 | 2.8 | 64 | 4350 | 0.206 | 289 | 263 |
3Cx185 | 3.4 | 2.9 | 67 | 4700 | 0.164 | 326 | 295 |
3Cx240 | 3.4 | 3.1 | 74 | 5600 | 0.125 | 394 | 347 |
3Cx300 | 3.4 | 3.3 | 79 | 6650 | 0.100 | 450 | 390 |
3Cx400 | 3.4 | 3.5 | 83 | 7250 | 0.0778 | 522 | 444 |
Three Core Cable(NA2XSEY)-8.7/15KV | |||||||
No. of cores and nominal cross section | Thickness of Insulation | Thickness of sheath | Approx. Overall Diameter | Approx. Weight | Max. DC Resistance of conductor(20℃) | Current Carrying Capacity | |
mm2 | mm | mm | mm | kg/km | Ω/km | in air(A) | in ground(A) |
3Cx70 | 4.5 | 2.7 | 58 | 3250 | 0.443 | 183 | 174 |
3Cx95 | 4.5 | 2.8 | 63 | 3900 | 0.32 | 222 | 208 |
3Cx120 | 4.5 | 2.9 | 66 | 4200 | 0.253 | 255 | 236 |
3Cx150 | 4.5 | 3 | 69 | 4700 | 0.206 | 289 | 263 |
3Cx185 | 4.5 | 3.1 | 73 | 5300 | 0.164 | 326 | 295 |
3Cx240 | 4.5 | 3.3 | 79 | 6300 | 0.125 | 394 | 347 |
3Cx300 | 4.5 | 3.4 | 84 | 7150 | 0.100 | 450 | 390 |
3Cx400 | 4.5 | 3.7 | 88 | 9700 | 0.0778 | 522 | 444 |
Three Core Cable(NA2XSEY)-12/20KV | |||||||
No. of cores and nominal cross section | Thickness of Insulation | Thickness of sheath | Approx. Overall Diameter | Approx. Weight | Max. DC Resistance of conductor(20℃) | Current Carrying Capacity | |
mm2 | mm | mm | mm | kg/km | Ω/km | in air(A) | in ground(A) |
3Cx70 | 5.5 | 2.8 | 63 | 3650 | 0.443 | 183 | 174 |
3Cx95 | 5.5 | 2.9 | 67 | 4200 | 0.32 | 222 | 208 |
3Cx120 | 5.5 | 3.0 | 70 | 4700 | 0.253 | 255 | 236 |
3Cx150 | 5.5 | 3.1 | 72.0 | 5200 | 0.206 | 289 | 263 |
3Cx185 | 5.5 | 3.3 | 78 | 5800 | 0.164 | 326 | 295 |
3Cx240 | 5.5 | 3.4 | 83 | 6900 | 0.125 | 394 | 347 |
3Cx300 | 5.5 | 3.6 | 88 | 7700 | 0.100 | 450 | 390 |
3Cx400 | 5.5 | 3.8 | 93 | 8200 | 0.0778 | 522 | 444 |
Three Core Cable(NA2XSEY)-18/30KV,19/33KV | |||||||
No. of cores and nominal cross section | Thickness of Insulation | Thickness of sheath | Approx. Overall Diameter | Approx. Weight | Max. DC Resistance of conductor(20℃) | Current Carrying Capacity | |
mm2 | mm | mm | mm | kg/km | Ω/km | in air(A) | in ground(A) |
3Cx70 | 8.0 | 3.2 | 75 | 4900 | 0.443 | 183 | 174 |
3Cx95 | 8.0 | 3.3 | 79 | 5500 | 0.32 | 222 | 208 |
3Cx120 | 8.0 | 3.4 | 82 | 6000 | 0.253 | 255 | 236 |
3Cx150 | 8.0 | 3.5 | 85.0 | 6500 | 0.206 | 289 | 263 |
3Cx185 | 8.0 | 3.6 | 89 | 7200 | 0.164 | 326 | 295 |
3Cx240 | 8.0 | 3.8 | 95 | 8400 | 0.125 | 394 | 347 |
3Cx300 | 8.0 | 4.0 | 100 | 9500 | 0.100 | 450 | 390 |