Contact
Applications
N2XSEBY cables are three-core class2 stranded copper medium voltage cables,the cables are mainly used for:
● Indoors and in cable ducts
● Outdoors,underground
● In power supply stations
● Transformer stations
● Industrial Plants
Using steel tape armouring offers great mechanical protection, making it rigid with a large radius installation indoors and outdoors.
For any more information or advice please contact the office on 0086-18832134509 (WhatsApp/WeChat)
Details
N2XSEBY medium voltage power cable, CU/XLPE/STA/PVC Cable
N2XSEBY(CU/XPLE/STA/PVC )medium voltage power cable with stranded compacted copper conductor is composed of copper conductor (CU), cross-linked polyethylene insulation (XPLE), Copper tape or copper wire screen, steel tape armoring for mechanical protection and a polyvinyl chloride sheath (PVC). N2XSEBY cables are suitable for for distribution networks,in fixed installation outdoors in cable ducts or directly in the ground, it widely used in transformer stations, electric power plants and industrial plants.
Construction
Descriptions:N2XSEBY Three Core MV Power Cable
Conductor:Copper, Class2,Circular compacted conductors
Conductor Screen: Non-metallic,semi-conducting compound
Insulation: Cross-linked polyethylene XLPE
Insulation Screen: Non-metallic,semi-conducting compound
Metallic Screen: Copper Tape Screend or Copper Wire Screened
Filler: Non-hygroscopic Material
Binder Tape: Non-hygroscopic Material
Armouring: Steel Tape Armour
Outer Sheath: Polyvinyl Chloride PVC&Polyethylene PE&LSZH
Physical Properties
Operating Temperature: up to 70℃(PVC insulation); up to 90℃(XLPE insulation)
Temperature Range: -5℃(PVC or LSZH sheath); -20℃(PE sheath)
Short Circuit Temperature(5 seconds maximum duration): 140℃-160℃(PVC insulation);250℃(XLPE insulation)
Nominal Voltages:U0/U 1.8/3kV , 6/10 kV, 12/20 kV, 18/30 kV
Technical Data
Three Core Cable(N2XSEBY)-6/10KV | |||||||
No. of cores and nominal cross section | Thickness of Insulation | Thickness of sheath | Approx. Overall Diameter | Approx. Weight | Max. DC Resistance of conductor(20℃) | Current Carrying Capacity | |
mm2 | mm | mm | mm | kg/km | Ω/km | in air(A) | in ground(A) |
3Cx35 | 3.4 | 2.4 | 50 | 3500 | 0.5240 | 154 | 151 |
3Cx50 | 3.4 | 2.5 | 53 | 4000 | 0.3870 | 183 | 178 |
3Cx70 | 3.4 | 2.6 | 57 | 5000 | 0.2680 | 225 | 215 |
3Cx95 | 3.4 | 2.7 | 60 | 5850 | 0.1930 | 272 | 257 |
3Cx120 | 3.4 | 2.9 | 64 | 7150 | 0.1530 | 310 | 290 |
3Cx150 | 3.4 | 3.0 | 68 | 8200 | 0.1240 | 348 | 323 |
3Cx185 | 3.4 | 3.1 | 71 | 9300 | 0.0991 | 396 | 363 |
3Cx240 | 3.4 | 3.3 | 78 | 11500 | 0.0754 | 462 | 418 |
3Cx300 | 3.4 | 3.4 | 83 | 13550 | 0.0601 | 523 | 467 |
3Cx400 | 3.4 | 3.6 | 86 | 17400 | 0.0470 | 582 | 515 |
Three Core Cable(N2XSEBY)-8.7/15KV | |||||||
No. of cores and nominal cross section | Thickness of Insulation | Thickness of sheath | Approx. Overall Diameter | Approx. Weight | Max. DC Resistance of conductor(20℃) | Current Carrying Capacity | |
mm2 | mm | mm | mm | kg/km | Ω/km | in air(A) | in ground(A) |
3Cx35 | 4.5 | 2.6 | 55 | 4100 | 0.5240 | 154 | 151 |
3Cx50 | 4.5 | 2.7 | 57 | 4500 | 0.3870 | 183 | 178 |
3Cx70 | 4.5 | 2.8 | 61 | 5500 | 0.2680 | 225 | 215 |
3Cx95 | 4.5 | 2.9 | 66 | 6500 | 0.1930 | 272 | 257 |
3Cx120 | 4.5 | 3.0 | 69 | 7600 | 0.1530 | 310 | 290 |
3Cx150 | 4.5 | 3.1 | 73 | 8700 | 0.1240 | 348 | 323 |
3Cx185 | 4.5 | 3.3 | 77 | 9950 | 0.0991 | 396 | 363 |
3Cx240 | 4.5 | 3.4 | 81 | 12200 | 0.0754 | 462 | 418 |
3Cx300 | 4.5 | 3.6 | 88 | 15000 | 0.0601 | 523 | 467 |
3Cx400 | 4.5 | 3.8 | 92 | 18500 | 0.0470 | 582 | 515 |
Three Core Cable(N2XSEBY)-12/20KV | |||||||
No. of cores and nominal cross section | Thickness of Insulation | Thickness of sheath | Approx. Overall Diameter | Approx. Weight | Max. DC Resistance of conductor(20℃) | Current Carrying Capacity | |
mm2 | mm | mm | mm | kg/km | Ω/km | in air(A) | in ground(A) |
3Cx35 | 5.5 | 2.8 | 59 | 4300 | 0.5240 | 154 | 151 |
3Cx50 | 5.5 | 2.9 | 62 | 5000 | 0.3870 | 183 | 178 |
3Cx70 | 5.5 | 3.0 | 66 | 5800 | 0.2680 | 225 | 215 |
3Cx95 | 5.5 | 3.2 | 68 | 7000 | 0.1930 | 272 | 257 |
3Cx120 | 5.5 | 3.3 | 70 | 7850 | 0.1530 | 310 | 290 |
3Cx150 | 5.5 | 3.4 | 74 | 9150 | 0.1240 | 348 | 323 |
3Cx185 | 5.5 | 3.5 | 80 | 10500 | 0.0991 | 396 | 363 |
3Cx240 | 5.5 | 3.7 | 88 | 13550 | 0.0754 | 462 | 418 |
3Cx300 | 5.5 | 3.9 | 92 | 15850 | 0.0601 | 523 | 467 |
3Cx400 | 5.5 | 4.0 | 96 | 18300 | 0.0470 | 582 | 515 |
Three Core Cable(N2XSEBY)-18/30KV,19/33KV | |||||||
No. of cores and nominal cross section | Thickness of Insulation | Thickness of sheath | Approx. Overall Diameter | Approx. Weight | Max. DC Resistance of conductor(20℃) | Current Carrying Capacity | |
mm2 | mm | mm | mm | kg/km | Ω/km | in air(A) | in ground(A) |
3Cx50 | 8.0 | 3.2 | 75 | 6650 | 0.3870 | 183 | 178 |
3Cx70 | 8.0 | 3.3 | 78 | 7650 | 0.2680 | 225 | 215 |
3Cx95 | 8.0 | 3.5 | 83 | 8700 | 0.1930 | 272 | 257 |
3Cx120 | 8.0 | 3.6 | 87 | 10700 | 0.1530 | 310 | 290 |
3Cx150 | 8.0 | 3.7 | 90 | 11750 | 0.1240 | 348 | 323 |
3Cx185 | 8.0 | 3.9 | 94 | 13500 | 0.0991 | 396 | 363 |
3Cx240 | 8.0 | 4.0 | 100 | 15500 | 0.0754 | 462 | 418 |
3Cx300 | 8.0 | 4.2 | 106 | 17800 | 0.0601 | 523 | 467 |