N2XSEY Three Core Medium Voltage Cable

Applications

N2XSEY cables are three-core class 2 stranded copper medium voltage cables, the cables are mainly used for: 

Indoors and in cable ducts

Outdoors,underground

In power supply stations

Transformer stations

Industrial Plants

Due to the good laying characteristic, this cable can also be installed in difficult line guideways.

The inner conducting layer between the conductor and the XLPE insulation and the firmly bonded outer conducting layer on the XLPE insulation assures a construction free of partial discharges with high operational reliabilities.

For any more information or advice please contact the office on 0086-18832134509 (WhatsApp/WeChat)

Share:

Details

Overview

CU/XLPE/CTS/PVC Cable

N2XSEY cables are three-core class 2 stranded copper medium voltage cables, they are the three-core variants of the cable N2XSY where the 'E' in the designation refers to each of the three cores being individually screened. 

N2XSEY have a cross-linked polyethylene (XLPE) insulation, copper tape screen, and a polyvinyl chloride (PVC) oversheath.The inner conducting layer between the conductor and the XLPE insulation and the firmly bonded outer conducting layer on the XLPE insulation assures a construction free of partial discharges with high operational reliabilities.

The N2XSEY offers a low factor of dielectric loss and excellent insulation property of XLPE for high operational reliability, which makes the N2XSEY cables are widely used in the building and construction, renewable energy, and power transmission industries where the cables can be laid directly into the ground or cable ducts.

Construction 

 N2XSEY Three Core Medium Voltage Cable

Descriptions:N2XSEY Three Core MV Power Cable

Conductor:Copper, Class2,Circular compacted conductors

Conductor Screen: Non-metallic,semi-conducting compound

Insulation: Cross-linked polyethylene XLPE

Insulation Screen: Non-metallic,semi-conducting compound

Metallic Screen: Copper Tape

Filler: Non-hygroscopic Material

Binder Tape: Non-hygroscopic Material

Outer Sheath: Polyvinyl Chloride PVC&Polyethylene PE&LSZH

Physical Properties

Operating Temperature: up to 70℃(PVC insulation); up to 90℃(XLPE insulation)

Temperature Range: -5℃(PVC or LSZH sheath); -20℃(PE sheath)

Short Circuit Temperature(5 seconds maximum duration): 140℃-160℃(PVC insulation);250℃(XLPE insulation)

Nominal Voltages:U0/U 1.8/3kV , 6/10 kV, 12/20 kV, 18/30 kV 

Technical Data

Three Core Cable(N2XSEY)-6/10KV
No. of cores and nominal cross sectionThickness of InsulationThickness of sheathApprox. Overall DiameterApprox. WeightMax. DC Resistance of conductor(20℃)Current Carrying Capacity
mm2mmmmmmkg/kmΩ/kmin air(A)in ground(A)
3Cx353.42.34627000.5240 158155
3Cx503.42.44932000.3870 189183
3Cx703.42.55240000.2680 235224
3Cx953.42.65649000.1930 286267
3Cx1203.42.76058000.1530 328303
3Cx1503.42.863 66500.1240 372339
3Cx1853.42.96781000.0991 418378
3Cx2403.43.1 7399500.0754 502442
3Cx3003.43.3 78120000.0601 572495
3Cx4003.43.581139000.0470 657558
Three Core Cable(N2XSEY)-8.7/15KV
No. of cores and nominal cross sectionThickness of InsulationThickness of sheathApprox. Overall DiameterApprox. WeightMax. DC Resistance of conductor(20℃)Current Carrying Capacity
mm2mmmmmmkg/kmΩ/kmin air(A)in ground(A)
3Cx354.52.55030000.5240 158155
3Cx504.52.65236000.3870 189183
3Cx704.52.75646000.2680 235224
3Cx954.52.86055000.1930 286267
3Cx1204.52.96364500.1530 328303
3Cx1504.53.0 65 73500.1240 372339
3Cx1854.53.1 7284000.0991 418378
3Cx2404.53.3 76101000.0754 502442
3Cx3004.53.4 82125000.0601 572495
3Cx4004.53.787154000.0470 657558
Three Core Cable(N2XSEY)-12/20KV
No. of cores and nominal cross sectionThickness of InsulationThickness of sheathApprox. Overall DiameterApprox. WeightMax. DC Resistance of conductor(20℃)Current Carrying Capacity
mm2mmmmmmkg/kmΩ/kmin air(A)in ground(A)
3Cx355.52.65634000.5240 158155
3Cx505.52.75938000.3870 189183
3Cx705.52.86347000.2680 235224
3Cx955.52.96656500.1930 286267
3Cx1205.53.0 7066500.1530 328303
3Cx1505.53.1 73 77000.1240 372339
3Cx1855.53.3 7890000.0991 418378
3Cx2405.53.4 83108000.0754 502442
3Cx3005.53.6 88128000.0601 572495
3Cx4005.53.893155000.0470 657558
Three Core Cable(N2XSEY)-18/30KV,19/33KV
No. of cores and nominal cross sectionThickness of InsulationThickness of sheathApprox. Overall DiameterApprox. WeightMax. DC Resistance of conductor(20℃)Current Carrying Capacity
mm2mmmmmmkg/kmΩ/kmin air(A)in ground(A)
3Cx5083.17151000.3870 189183
3Cx708.03.27660000.2680 235224
3Cx958.03.37872000.1930 286267
3Cx1208.03.4 8280500.1530 328303
3Cx1508.03.5 85 91000.1240 372339
3Cx1858.03.6 89104000.0991 418378
3Cx2408.03.8 95126000.0754 502442
3Cx3008.04.0 100147000.0601 572495



Contact Us Now