NA2XSEBY MV Three Core Cable 18/30kV

Applications

NA2XSEBY cables are three-core class2 stranded aluminium medium voltage cables,the cables are mainly used for: 

 Indoors and in cable ducts

 Outdoors,underground 

 In power supply stations

 Transformer stations

 Industrial Plants

Using steel tape armouring offers great mechanical protection, making it rigid with a large radius installation indoors and outdoors.

For any more information or advice please contact the office on 0086-18832134509 (WhatsApp/WeChat)

Share:

Details

Overview

NA2XSEBY medium voltage power cable, AL/XLPE/STA/PVC Cable

 NA2XSEBY(AL/XPLE/STA/PVC )medium voltage power cable with stranded compacted aluminium conductor is composed of aluminium conductor (AL), cross-linked polyethylene insulation (XPLE), Copper tape or copper wire screen, steel tape armoring for mechanical protection and a polyvinyl chloride sheath (PVC). NA2XSEBY cables are suitable for for distribution networks,in fixed installation outdoors in cable ducts or directly in the ground, it widely used in transformer stations, electric power plants and industrial plants.

Construction 

Descriptions:NA2XSEBY Three Core MV Power Cable

Conductor:Aluminium, Class2,Circular compacted conductors

Conductor Screen: Non-metallic,semi-conducting compound

Insulation: Cross-linked polyethylene XLPE

Insulation Screen: Non-metallic,semi-conducting compound

Metallic Screen: Copper Tape Screend or Copper Wire Screened

Filler: Non-hygroscopic Material

Binder Tape: Non-hygroscopic Material

Armouring: Steel Tape Armour

Outer Sheath: Polyvinyl Chloride PVC&Polyethylene PE&LSZH

Physical Properties

Operating Temperature: up to 70℃(PVC insulation); up to 90℃(XLPE insulation)

Temperature Range: -5℃(PVC or LSZH sheath); -20℃(PE sheath)

Short Circuit Temperature(5 seconds maximum duration): 140℃-160℃(PVC insulation);250℃(XLPE insulation)

Nominal Voltages:U0/U 1.8/3kV , 6/10 kV, 12/20 kV, 18/30 kV 

Technical Data

Three Core Cable(NA2XSEBY)-12/20KV
No. of cores and nominal cross sectionThickness of InsulationThickness of sheathApprox. Overall DiameterApprox. WeightMax. DC Resistance of conductor(20℃)Current Carrying Capacity
mm2mmmmmmkg/kmΩ/kmin air(A)in ground(A)
3Cx705.536748500.443175167
3Cx955.53.17154000.32211199
3Cx1205.53.2 7560000.253241226
3Cx1505.53.3 78.0 65000.206271251
3Cx1855.53.4 8172000.164310284
3Cx2405.53.7 8991500.125364329
3Cx3005.53.8 94103000.100 413369
3Cx4005.54.0 96118000.0778470415
Three Core Cable(NA2XSEBY)-18/30KV,19/33KV
No. of cores and nominal cross sectionThickness of InsulationThickness of sheathApprox. Overall DiameterApprox. WeightMax. DC Resistance of conductor(20℃)Current Carrying Capacity
mm2mmmmmmkg/kmΩ/kmin air(A)in ground(A)
3Cx708.03.37762000.443175167
3Cx958.03.58270000.32211199
3Cx1208.03.6 8684000.253241226
3Cx1508.03.7 89.0 90000.206271251
3Cx1858.03.9 9398500.164310284
3Cx2408.04.0 100111000.125364329
3Cx3008.04.2 104124000.100 413369


Contact Us Now