NA2XSERY Three Core Medium Voltage Power Cable

Applications

The three core cables NA2XSERY are designed for distribution of electrical power with nominal voltage Uo/U ranging from 1.8/3KV to 26/35KV and frequency 50Hz. They are suitable for use for: 

 Intdoors and in cable ducts

 Outdoors,underground 

● Switch-boards and power stations

 Transformer stations

 Industrial Plants

 Due to the good laying and mechanical characteristic, this cable is suitable when mechanical protection is required or in applications where mechanical damages are expected to occur.

 For any more information or advice please contact the office on 0086-18832134509 (WhatsApp/WeChat)

Share:

Details

Overview

AL/XLPE/CWS/PVC/SWA/PVC Cable  

NA2XSERY Medium Voltage 3 Cores AL/XLPE/CWS/PVC/SWA/PVC Armoured Power Cable is for power transmission in industrial and construction applications. This cable NA2XSERY offers a design with a aluminium core for superior conductivity and heat dissipation. NA2XSERY features XLPE insulation, PVC jacket, and a SWA armoured construction, providing improved durability and protection against harsh environmental conditions. The three core cables NA2XSERY are designed for distribution of electrical power with nominal voltage Uo/U ranging from 1.8/3KV to 26/35KV and frequency 50Hz. Made with a layer of steel wire armoured (SWA), polyethylene (XLPE) thermosetting insulation, and hard-wearing PVC, these armoured cables can withstand twisting, crushing, impacts, temperature extremes, moisture, chemical hazards, and more. N2XSERY are suitable for use in a range of environments, from industrial installations and manufacturing facilities to construction sites,and other medium-voltage electrical systems.

Construction 

NA2XSERY Three Core Medium Voltage Power Cable

Descriptions:NA2XSERY Three Core MV Power Cable

Conductor:Aluminium, Class2,Circular compacted conductors

Conductor Screen: Non-metallic,semi-conducting compound

Insulation: Cross-linked polyethylene XLPE

Insulation Screen: Non-metallic,semi-conducting compound

Metallic Screen: Copper Tape

Filler: Non-hygroscopic Material

Binder Tape: Non-hygroscopic Material

Armouring: Steel Wire Armour

Outer Sheath: Polyvinyl Chloride PVC&Polyethylene PE&LSZH

Physical Properties

Operating Temperature: up to 70℃(PVC insulation); up to 90℃(XLPE insulation)

Temperature Range: -5℃(PVC or LSZH sheath); -20℃(PE sheath)

Short Circuit Temperature(5 seconds maximum duration): 140℃-160℃(PVC insulation);250℃(XLPE insulation)

Nominal Voltages:U0/U 1.8/3kV , 6/10 kV, 12/20 kV, 18/30 kV 

Technical Data

Three Core Cable(NA2XSERY)-6/10KV
No. of cores and nominal cross sectionThickness of InsulationThickness of sheathApprox. Overall DiameterApprox. WeightMax. DC Resistance of conductor(20℃)Current Carrying Capacity
mm2mmmmmmkg/kmΩ/kmin air(A)in ground(A)
3Cx703.42.75853000.443172165
3Cx953.42.96368000.32208196
3Cx1203.43.0 66 67000.253238222
3Cx1503.43.17075000.206268248
3Cx1853.43.27381000.164306280
3Cx2403.43.4 79104000.125359322
3Cx3003.43.6 85114000.1000 406360
3Cx4003.43.993137000.0778 468407
Three Core Cable(NA2XSERY)-8.7/15KV
No. of cores and nominal cross sectionThickness of InsulationThickness of sheathApprox. Overall DiameterApprox. WeightMax. DC Resistance of conductor(20℃)Current Carrying Capacity
mm2mmmmmmkg/kmΩ/kmin air(A)in ground(A)
3Cx704.52.96460000.443172165
3Cx954.53.0 6870000.32208196
3Cx1204.53.27275000.253238222
3Cx1504.53.375 91000.206268248
3Cx1854.53.4 80100000.164306280
3Cx2404.53.6 86113000.125359322
3Cx3004.53.8 92125000.1000 406360
3Cx4004.54.0 96128000.0778 468407
Three Core Cable(NA2XSERY)-12/20KV
No. of cores and nominal cross sectionThickness of InsulationThickness of sheathApprox. Overall DiameterApprox. WeightMax. DC Resistance of conductor(20℃)Current Carrying Capacity
mm2mmmmmmkg/kmΩ/kmin air(A)in ground(A)
3Cx705.53.16860000.443172165
3Cx955.53.27368000.32208196
3Cx1205.53.3 7877000.253238222
3Cx1505.53.5 82 92500.206268248
3Cx1855.53.6 86100000.164306280
3Cx2405.53.7 91108000.125359322
3Cx3005.53.9 96121000.1000 406360
3Cx4005.54.1 100134000.0778 468407
Three Core Cable(NA2XSERY)-18/30KV,19/33KV
No. of cores and nominal cross sectionThickness of InsulationThickness of sheathApprox. Overall DiameterApprox. WeightMax. DC Resistance of conductor(20℃)Current Carrying Capacity
mm2mmmmmmkg/kmΩ/kmin air(A)in ground(A)
3Cx708.03.58396000.443172165
3Cx958.03.687105000.32208196
3Cx1208.03.7 90111500.253238222
3Cx1508.03.9 94 121000.206268248
3Cx1858.04.0 98130000.164306280
3Cx2408.04.1 103143000.125359322
3Cx3008.04.3 109157000.1000 406360