Contact
Applications
NA2XSRY(AL/XLPE/SWA/PVC) is a single core aluminium medium voltage cable with cross-linked polyethylene (XLPE) insulation, steel wire armouring, and a polyvinyl chloride (PVC) oversheath. These armoured cables can withstand twisting, crushing, impacts, temperature extremes, moisture, chemical hazards, and more. They're suitable for use in a range of environments, widely used in the construction and power distribution industries. NA2XSRY cables are mainly used for:
● Intdoors and in cable ducts
● Outdoors,underground
● Switch-boards and power stations
● Transformer stations
● Industrial Plants
NA2XSRY cable is suitable when mechanical protection is required or in applications where low mechanical damages are expected to occur.
For any more information or advice please contact the office on 0086-18832134509 (WhatsApp/WeChat)
Details
AL/XLPE/SWA/PVC Cable
NA2XSRY(AL/XLPE/SWA/PVC) is a single core aluminium medium voltage cable with cross-linked polyethylene (XLPE) insulation, steel wire armouring, and a polyvinyl chloride (PVC) oversheath. These armoured cables can withstand twisting, crushing, impacts, temperature extremes, moisture, chemical hazards, and more. They're suitable for use in a range of environments, widely used in the construction and power distribution industries. Armoured Power Cables are the perfect choice when you need the toughest and most durable armoured cable for power distribution and transmission.
Other than for its aluminium conductor, the NA2XSRY shares the same cable construction as its copper variant, the N2XSRY cable and are manufactured in accordance with IEC 60502-2 and DIN EN 60228. NA2XSRY is a cost-efficient alternative to its copper variant on installations where space is not an issue due to the larger overall diameter of aluminium cables. NA2XSRY cable voltages rating is 6/10kV, 12/20kV, or 18/30kV.
Construction
Descriptions:NA2XSRY Single Core Steel wire armoured MV Power Cable
Conductor:Aluminum, Class2,Circular compacted conductors
Conductor Screen: Non-metallic,semi-conducting compound
Insulation: Cross-linked polyethylene XLPE
Insulation Screen: Non-metallic,semi-conducting compound
Metallic Screen: Copper Tape
Inner Sheathing: Non-metallic,semi-conducting compound
Armouring: Non-magnetic Steel Wire Armour
Outer Sheath: Polyvinyl Chloride PVC&Polyethylene PE&LSZH
Physical Properties
Operating Temperature: up to 70℃(PVC insulation); up to 90℃(XLPE insulation)
Temperature Range: -5℃(PVC or LSZH sheath); -20℃(PE sheath)
Short Circuit Temperature(5 seconds maximum duration): 140℃-160℃(PVC insulation);250℃(XLPE insulation)
Nominal Voltages:U0/U 6/10 kV, 12/20 kV, 18/30 kV
Technical Data
Single Core Cable(NA2XSRY)-6/10KV | |||||||
No. of cores and nominal cross section | Thickness of Insulation | Thickness of sheath | Approx. Overall Diameter | Approx. Weight | Max. DC Resistance of conductor(20℃) | Current Carrying Capacity | |
mm2 | mm | mm | mm | kg/km | Ω/km | in air(A) | in ground(A) |
1x70 | 3.4 | 1.9 | 31 | 1160 | 0.443 | 213 | 175 |
1x95 | 3.4 | 1.9 | 32 | 1320 | 0.32 | 258 | 208 |
1x120 | 3.4 | 2.0 | 34 | 1470 | 0.253 | 294 | 235 |
1x150 | 3.4 | 2.1 | 36 | 1670 | 0.206 | 329 | 260 |
1x185 | 3.4 | 2.1 | 38 | 1840 | 0.164 | 373 | 291 |
1x240 | 3.4 | 2.2 | 40 | 2140 | 0.125 | 432 | 332 |
1x300 | 3.4 | 2.2 | 42 | 2410 | 0.1000 | 486 | 369 |
1x400 | 3.4 | 2.4 | 46 | 2890 | 0.0778 | 547 | 408 |
1x500 | 3.4 | 2.5 | 51 | 3540 | 0.0605 | 611 | 451 |
1x630 | 3.4 | 2.6 | 55 | 4130 | 0.0469 | 675 | 494 |
Single Core Cable(NA2XSRY)-8.7/15KV | |||||||
No. of cores and nominal cross section | Thickness of Insulation | Thickness of sheath | Approx. Overall Diameter | Approx. Weight | Max. DC Resistance of conductor(20℃) | Current Carrying Capacity | |
mm2 | mm | mm | mm | kg/km | Ω/km | in air(A) | in ground(A) |
1x70 | 4.5 | 2.0 | 33 | 1300 | 0.443 | 213 | 175 |
1x95 | 4.5 | 2.0 | 35 | 1520 | 0.32 | 258 | 208 |
1x120 | 4.5 | 2.1 | 37 | 1680 | 0.253 | 294 | 235 |
1x150 | 4.5 | 2.1 | 38 | 1830 | 0.206 | 329 | 260 |
1x185 | 4.5 | 2.2 | 40 | 2020 | 0.164 | 373 | 291 |
1x240 | 4.5 | 2.3 | 43 | 2330 | 0.125 | 432 | 332 |
1x300 | 4.5 | 2.3 | 45 | 2610 | 0.1000 | 486 | 369 |
1x400 | 4.5 | 2.5 | 51 | 3280 | 0.0778 | 547 | 408 |
1x500 | 4.5 | 2.6 | 54 | 3800 | 0.0605 | 611 | 451 |
1x630 | 4.5 | 2.7 | 58 | 4390 | 0.0469 | 675 | 494 |
Single Core Cable(NA2XSRY)-12/20KV | |||||||
No. of cores and nominal cross section | Thickness of Insulation | Thickness of sheath | Approx. Overall Diameter | Approx. Weight | Max. DC Resistance of conductor(20℃) | Current Carrying Capacity | |
mm2 | mm | mm | mm | kg/km | Ω/km | in air(A) | in ground(A) |
1x70 | 5.5 | 2.0 | 35 | 1480 | 0.443 | 213 | 175 |
1x95 | 5.5 | 2.1 | 37 | 1680 | 0.32 | 258 | 208 |
1x120 | 5.5 | 2.1 | 39 | 1820 | 0.253 | 294 | 235 |
1x150 | 5.5 | 2.2 | 40 | 2000 | 0.206 | 329 | 260 |
1x185 | 5.5 | 2.2 | 42 | 2180 | 0.164 | 373 | 291 |
1x240 | 5.5 | 2.3 | 45 | 2500 | 0.125 | 432 | 332 |
1x300 | 5.5 | 2.4 | 48 | 2970 | 0.1000 | 486 | 369 |
1x400 | 5.5 | 2.5 | 53 | 3480 | 0.0778 | 547 | 408 |
1x500 | 5.5 | 2.6 | 56 | 4000 | 0.0605 | 611 | 451 |
1x630 | 5.5 | 2.8 | 60 | 4630 | 0.0469 | 675 | 494 |
Single Core Cable(NA2XSRY)-18/30KV,19/33KV | |||||||
No. of cores and nominal cross section | Thickness of Insulation | Thickness of sheath | Approx. Overall Diameter | Approx. Weight | Max. DC Resistance of conductor(20℃) | Current Carrying Capacity | |
mm2 | mm | mm | mm | kg/km | Ω/km | in air(A) | in ground(A) |
1x70 | 8.0 | 2.2 | 41 | 1900 | 0.443 | 213 | 175 |
1x95 | 8.0 | 2.3 | 43 | 2100 | 0.32 | 258 | 208 |
1x120 | 8.0 | 2.3 | 44 | 2260 | 0.253 | 294 | 235 |
1x150 | 8.0 | 2.4 | 47 | 2600 | 0.206 | 329 | 260 |
1x185 | 8.0 | 2.5 | 49 | 2830 | 0.164 | 373 | 291 |
1x240 | 8.0 | 2.5 | 51 | 3160 | 0.125 | 432 | 332 |
1x300 | 8.0 | 2.6 | 54 | 3530 | 0.1000 | 486 | 369 |
1x400 | 8.0 | 2.7 | 58 | 4080 | 0.0778 | 547 | 408 |
1x500 | 8.0 | 2.8 | 62 | 4650 | 0.0605 | 611 | 451 |
1x630 | 8.0 | 2.9 | 65 | 5280 | 0.0469 | 675 | 494 |