NA2XSY 18/30KV Cable

Applications

The NA2XSY (medium voltage)has a single core aluminium stranded class 2 conductor with cross-linked polyethylene (XLPE) insulation, copper wire metallic screen, and polyvinyl chloride (PVC) oversheath.They are mainly used for: 

 Indoors and in cable ducts

 Outdoors,underground 

 In power supply stations

 Transformer stations

 Industrial Plants

Due to the good laying characteristic, this cable can also be installed in difficult line guideways.

The inner conducting layer between the conductor and the XLPE insulation and the firmly bonded outer conducting layer on the XLPE insulation assures a construction free of partial discharges with high operational reliabilities.

For any more information or advice,please contact the office on 0086-18832134509(WhatsApp/WeChat)

Share:

Details

Overview

AL/XLPE/CWS/PVC Cable

The NA2XSY (medium voltage)has a single core aluminium stranded class 2 conductor with cross-linked polyethylene (XLPE) insulation, copper wire metallic screen, and polyvinyl chloride (PVC) oversheath. NA2XSY cable is widely used in internal/external power distribution networks,external where it's either direct buried or installed into cable ducting, but also it can be run and terminated inside a building as the NA2XSY cable is flame retardant.

The NA2XSY provides long-term operational reliability due to a low dielectric loss factor and excellent insulation property of XLPE, which makes it widely used in transformer stations, electric power plants and industrial plants. Nevertheless, it should be used in fixed installations to avoid mechanical or tensile strain.

Construction 

 NA2XSY 18/30KV Cable

Descriptions:NA2XSY Single Core MV Power Cable

Conductor:Aluminum, Class2,Circular compacted conductors

Conductor Screen: Non-metallic,semi-conducting compound

Insulation: Cross-linked polyethylene XLPE

Insulation Screen: Non-metallic,semi-conducting compound

Metallic Screen: Copper Wire with Copper Tape

Outer Sheath: Polyvinyl Chloride PVC&Polyethylene PE&LSZH

Physical Properties

Operating Temperature: up to 70℃(PVC insulation); up to 90℃(XLPE insulation)

Temperature Range: -5℃(PVC or LSZH sheath); -20℃(PE sheath)

Short Circuit Temperature(5 seconds maximum duration): 140℃-160℃(PVC insulation);250℃(XLPE insulation)

Nominal Voltages:U0/U 6/10 kV, 12/20 kV, 18/30 kV

Technical Data

Single Core Cable(NA2XSY)-18/30KV,19/33KV
No. of cores and nominal cross sectionThickness of InsulationThickness of sheathApprox. Overall DiameterApprox. WeightMax. DC Resistance of conductor(20℃)Current Carrying Capacity
mm2mmmmmmkg/kmΩ/kmin air(A)in ground(A)
1x358.01.930.19230.868185134
1x508.02.031.310090.641222157
1x708.02.033.211490.443278192
1x958.02.13513010.32338229
1x1208.02.1 36.414300.253391260
1x1508.02.2 37.9 15730.206440288
1x1858.02.2 39.717440.164504324
1x2408.02.3 42.320120.125593373
1x3008.02.4 44.622810.100 677419
1x4008.02.547.526470.0778769466
1x5008.02.650.931010.0605872573


Contact Us Now